3
INSTALLATION INSTRUCTIONS
3.4
3.5
3.6
Power Metering products online at:
List of Materials
•
Line 1, Line 2, and Neutral hook-up wires provided.
•
Field wire requirements: 14 to 18 AWG min., 300 V min. insulated. Temperature
rating should be consistent with the operating environment.
Mounting Location
Mini Meters require a switch or circuit breaker as part of the building installation.
•
The switch or circuit breaker must be marked as the disconnecting device for the
meter.
•
The meter should be mounted near the disconnecting device, in an area with
adequate ventilation and not in direct sun to prevent overheating of the meter.
The meter and CT's should be kept away from transformers and radio equipment.
•
The meter enclosure should not be positioned in a manner that makes it difficult
to operate the disconnecting device.
•
Ensure that the CT and voltage lead lengths (and conduit lengths) are capable of
reaching the enclosure from the breaker panel.
•
If a suitable mounting location near the panel cannot be found, additional in-
line fuses or circuit breaker may be required in accordance with NEC or local
regulations.
Physical Dimensions
Figure 1 shows the dimensions of a single Mini Meter OEM Module case and
cover.
2.150
.125
Figure 1 - Mini Meter Dimensions, in inches
www.
4.620
3.525
5.130
5.130
5
PowerMeterStore
2.845
1.107 1.282
1.888.610.
.com