Interconnexions Capteur Xpp-5 - Siemens Milltronics MFA 4P Manuel D'utilisation

Détecteur de mouvement très fiable
Table des Matières

Publicité

Interconnexions capteur XPP-5

NON - HAZARDOUS LOCATION
NON - HAZARDOUS LOCATION
MILLTRONICS
CONTROLLER
MILLTRONICS
CONTROLLER
NOTES :
1) THE XPP-5 CABLE MUST BE TERMINATED IN AN AREA EXTERNAL
TO HAZARDOUS LOCATIONS, CLASS I, DIV 1, GR.
2) A SEAL SHALL BE INSTALLED WITHIN 50 mm OF THE XPP-5 CONDUIT HUB
FOR CLASS I, DIV. 1 HAZARDOUS LOCATION ONLY.
3) INSTALLATION SHALL BE DONE IN ACCORDANCE WITH
CANADIAN ELECTRICAL CODE PART 1 REQUIREMENTS.
4) DO NOT EXPOSE THE XPP-5 TO DIRECT SUNLIGHT, OTHERWISE
PROVIDE SUN SHIELD.
5) STATIC HAZARD, DO NOT RUB WITH DRY CLOTH.
N. T. S.
B. GRAY
R. CLOSS
S. NGUYEN
7ML19985FM11
HAZARDOUS LOCATION
HAZARDOUS LOCATION
CLASS I, DIV 1, GROUPS A,B,C,D
CLASS I, DIV 1, GROUPS A,B,C,D
CLASS II, DIV 1, GROUPS E,F,G
CLASS II, DIV 1, GROUPS E,F,G
METAL CONDUIT
CERTIFIED
CONDUIT
SEAL
FITTING
CERTIFIED
CONDUIT
SEAL
FITTING
A,B,C,D
& CLASS II, DIV 1, GR. E,F,G.
XPP-5
INTERCONNECTION DIAGRAM
MFA 4p – MANUEL D'UTILISATION
CERTIFIED
CONDUIT
SEAL
FITTING
JUNCTION BOX
CLASS I & II
METAL CONDUIT
CERTIFIED
REVISED HOUSING THREADS
2
PER ECN #00-000-0-0070
REVISED CABLE AND TERMINAL CONNECTOR
1
PER ECN #00-000-0-0037
0
FOR CONSTRUCTION
2365013102
1=1
XPP-5
CONDUIT
SEAL
FITTING
XPP-5
JULY
RWG
SN
11/00
APRIL
RWG
SN
18/00
MARCH
RWG
SN
27/00
23650131
2
1
1
Page 21

Publicité

Table des Matières
loading

Table des Matières