AirCon Service Center
3. Press ENTER to update the software or database.
✓ The station shows the progress of the update:
After the update, the station sets the default settings:
The station then restarts and the standby menu appears.
4. Remove the USB stick.
✓ The station is ready for operation.
9.11
Manual discharge of non-condensing gases
A
NOTICE!
The manual discharge of non-condensing gases may only be carried
out during the initial power-on on a given day. When the device is put
into operation, the internal pressures and temperatures change. This
makes the procedure described in this chapter too inaccurate.
1. Calibrate the pressure sensor so that the correct values are dis-
played (see chapter "Calibrating the pressure transducer" on
page 122).
✓ After switching on, the device measures the internal tank pressure
and then shows it in the display:
If you transfer the indicated pressure to the scale of the pressure
gauge of the device, you can read the corresponding temperature.
Example
The pressure gauge shows 7.6 bar (7600 mbar). The corresponding
temperature is approximately 34 °C.
EN
Wait...
Erase flash... Erased!
Writing
Wait!
loading default
parameters
Wait!
Internal vessel
pressure
1
63488
7%
762751
mb.
7600
Service tasks
129