For chillers equipped with two condensers (EB 180 - 220), follow the indications in figure 2b
Picture 2b – Room minimum dimensions
According to CEI EN 60204-1, for units which don't have the lockable main switch at a minimum distance of 0.6 m from the
basement of the unit, it's necessary to install that units in a position that allows to maintain that minimum distance.
CAUTION!
For standard unit the outdoor installation is absolutely forbidden, even if under a roof.
Only special designed outdoor units can be used in outdoor installation.
For regular maintenance or adjustment, the chiller shall be located between 0.3 m and 1.0 m above the servicing level.
PFANNENBERG chillers should be set on a concrete slab. The slab should extend a minimum of 30 cm (12 inches) beyond the
perimeter of the Chiller to prevent damage from lawn maintenance equipment, etc. The Chiller, which should be level and properly
anchored, is provided with 4 antivibration dampers on the bottom of the unit, which allow the support and the fixing of the Chiller
and to dampen the vibrations and decrease the noise during the operation.