N°REG.
Register
8
Ki
EN
9
Kq
10
PulsosEncoder
11
MinOut
12
MaxOut
13
S1Alarm
14
S2Alarm
15
MinRPM
16
VacMIN
17
IN1 Range
18
IN2 Range
19
IN1 Set
20
IN1 Banda
21
IN2 Set
22
IN2 Banda
23
InD
24
setMODBUS
25
IDIOMA
26
SP-2 PRESION
27
SP-2 CAUDAL
28
SP Temp
29
adMODBUS
26
Min.
Max.
Description
1
250
Increases 1
50
300
Increases 1
0
16
Increases 1
0
50
Increases 5%
50
100
Increases 5%
0
100
Increases 5%
0
100
Increases 5%
100
500
Increases de 100
80
150
Increases de 10
0
100
%HR increases
0
50
°C increases
0
2000
PPM increases
0
100
%HR increases
0
50
°C increases
0
2000
PPM increases
0
IN1 Range
Increases de 1
0
IN1 Range
Increases de 1
0
IN2 Range
Increases de 1
0
IN2 Range
Increases de 1
0
1
1
PIRange
Increases de 50
0=ENGLISH
1=SPANISH
0
3
2=FRENCH
3=GERMAN
25
100
Increases de 1
50
100
Increases de 1
-10
50
Increases de 1
1
247
Increases de 1
0
100
Default
20
100
(CTB/4-500/200)
84
(CTB/4-800/250)
94
(CTB/4-1300/315)
123
(CRVB-CRHB/4-315)
155
(CRVB-CRHB/4-355)
197
(CRVB-CRHB/4-400)
2
(CTB/4-400/160)
(CTB/4-500/200)
5
(CTB/4-800/250)
(CTB/4-1300/315)
3
(CRVB-CRHB/4-315)
(CRVB-CRHB/4-355)
(CRVB-CRHB/4-400)
0
100
90
90
400
80
100
100
50
25
50
25
0=NO
0
1=NC
0
0
25
50
1
Comments
Integral constant in PI
PRESSURE mode
Airflow constant with
pressure sensor
Number of pulses for
encoder lap
Minimum output value
Maximum output value
Analog input 1 alarm
Analog input 2 alarm
Min RPM alarm
Minimum voltage AC
motor
Background scale in
proportional mode input 1
Background scale in
proportional mode input 2
Set point proportional
mode input 1
Margin (+/-) centered in
IN1 Set
Set point proportional
mode input 2
Margin (+/-) centered
in IN2 Set
Digital input inverter
MODBUS set point
Language
Night set point in PI
PRESSURE mode
Night set point in PI
VOLUME mode
Temperature set point
(only for CTBH ECOWATT
models)