SN2008/AST4, SN2008/AST4-F
Rough-In Dimensions for Supplies and Drain
Notes
Maximum flow rate required to washfountain is 1 .5 GPM . Size supply
lines accordingly .
Supplies from Below: Stub up 2-1/2" (64) .
Supplies from Above: Supplies must be located on centers of dimensions
shown to pass through washfountain shroud and sprayhead .
Drain through floor: Stub up 3" (76) .
Supplies from Below or Through Wall
3-1/4" (83)
UPC and IPC restrict the vertical distance from the fixture outlet to the trap
weir to not more than 24" (610). Check state and local codes for variances.
4
Type A
Off-line vent (P-Trap
supplied by Installer .)
Type H
Centrally rising vent (P-Trap
furnished with unit .) Use
for units with paper towel
Dispensers and/or shrouds .
Top View
4-1/2"
4-1/2"
(114)
(114)
H
C
Type H
5"
(127)
Type A
8/18/2014
Key
1/2" Supply: Nominal Copper Tube
1-1/2" NPT Drain Stub up 3" (76) from
Floor
Supplies from Above
Type B
Centrally rising vent (P-Trap
furnished with unit .) Use
for units with paper towel
Dispensers and/or shrouds .
Type O
Off-line vent (P-Trap supplied
by Installer .)
Top View
H
27/32" (21)
27/32" (21)
5"
(127)
C
1-3/16"
(30)
Bradley • 215-1068 Rev. J; ECN 14-00-007
Installation
(mm)
Type B
Type O