Télécharger Imprimer la page

Napoleon Ascent 42 Serie Manuel D'installation Et D'utilisation page 56

Masquer les pouces Voir aussi pour Ascent 42 Serie:

Publicité

Les langues disponibles

Les langues disponibles

adjustments
EN
11.2
venturi adjustment
This appliance has an air shutter that has been factory set open according to
the chart below:
Regardless of venturi orientation, closing the air shutter will cause a more
yellow flame, but can lead to carbonization. Opening the air shutter will cause
a more blue flame, but can cause flame lifting from the burner ports. The flame
may not appear yellow immediately; allow 15 to 30 minutes for the final flame
colour to be established.
AIR SHUTTER ADJUSTMENT MUST ONLY BE DONE BY A QUALIFIED
INSTALLER.
note:
It is important that the orifice is securely inserted into the venturi.
VENTURI ADJUSTMENT CHART
FUEL
TOP
NG
1/16" (1.5mm)
P
3/8" (9.5mm)
11.3
flame characteristics
It's important to periodically perform a visual check of
the pilot and burner flames. Compare them to the
illustration provided. If any flames appear abnormal,
call a service person.
56
W415-3095 / A / 05.03.22
REAR
1/8" (3.1mm)
3/8" (9.5mm)
PSE THERMOCOUPLE
VENTURI
3/8" - 1/2"
BURNER
(9.5mm - 12.7mm)
Flame must envelop
upper
3/8" to 1/2"
(12.7mm - 9.5mm) of
thermocouple
ORIFICE
SIT ELECTRONIC IGNITION
3/8" - 1/2"
(9.5mm - 12.7mm)
Flame must envelop
upper
3/8" to 1/2"
(12.7mm - 9.5mm) of
Flame sensor
ADD IMAGE
HERE
SIT MILLIVOLT
3/8" - 1/2"
(9.5mm - 12.7mm)
36.1
Flame must envelop
upper
3/8" to 1/2"
(12.7mm - 9.5mm) of
thermocouple &
thermopile
PSE LONG SENSOR
3/8" - 1/2"
(9.5mm - 12.7mm)
Flame must envelop
upper
3/8" to 1/2"
(12.7mm - 9.5mm) of
thermocouple
AIR
SHUTTER
OPENING
33.1
(9.5
La flamm
la thermo
(9.5m
La fla
la s
(9
(9.
t
(9
(9.
La flamm
la thermo
(9.5m

Publicité

loading

Ce manuel est également adapté pour:

Ascent b42ntreaAscent b42ptrea