Télécharger Imprimer la page

Glen Dimplex LA 9S-TU Instructions D'installation Et D'utilisation page 32

Publicité

Les langues disponibles

Les langues disponibles

English
12 Device information
1
Type and order code
2
Design
Heat source
2.1
Model
2.2
Controller
2.3
Installation location
2.4
Thermal energy metering
2.5
Performance levels
3
Operating limits
3.1
Heating water flow / return
1
3.2
Air (heating)
4
4
Flow
/ sound
4.1
Heating water flow / internal pressure differential
Nominal flow in accordance with EN 14511
4.2
Minimum heating water flow rate
4.3
Sound power level according to EN 12102
Normal operation / reduced operation
4.4
Sound pressure level at a distance of 10 m (air outlet side)
Normal operation / reduced operation
4.5
Air flow
Normal operation / reduced operation
5
Dimensions, weight and filling quantities
5.1
Device dimensions without connections
5.2
Device connections for heating
5.3
Weight of the transportable unit(s) incl. packaging
5.4
Refrigerant / total filling weight
5.5
GWP value / CO
equivalent
2
5.6
Refrigeration circuit hermetically sealed
5.7
Lubricant / total filling quantity
5.8
Volume of heating water in device
6
Electrical connection
6.1
Supply voltage / fusing / RCD type
6.2
Control voltage / fusing by WPM
6.3
Degree of protection according to EN 60529
6.4
Starting current limiter
6.5
Rotary field monitoring
6.6
Starting current with soft starter
6.7
Nominal power consumption A2/W35 /
max. power consumption
Nominal current A2 /W35 / cos 
6.8
6.9
Power consumption of compressor protection
(per compressor)
6.10 Power consumption of fan
7
Complies with the European safety regulations
8
Additional model features
8.1
Type of defrosting
8.2
Frost protection, condensate tray /
Water in device protected against freezing
8.3
Maximum operating pressure (heat sink)
8.4
Energy efficiency class / energy efficiency (low temperature)
EN-10
1
at A7 / W35...30
at A7 / W45...40
at A7 / W55...47
6 7
6 7
7
4
10
452168.66.01a · FD 0102
LA 9S-TU
Air
Universal
WPM Econ 5S, wall-
mounted
Outdoors
Integrated
1
up to 60 ± 2 / from 18
°C
-22 to +35
°C
1.5 / 9900
m³/h / Pa
m³/h / Pa
1.4 / 8800
5
m³/h / Pa
0.9
/ 3600
m³/h / Pa
1.2 / 6400
53 / 53
dB(A)
8
25 / 25
dB(A)
2700 / 2100
m³/h
H x W x L mm
1650 x 910 x 750
inches
G 1 1/4" external thread G 1 1/4" external thread G 1 1/4" external thread
kg
225
type/kg
R410A / 3.9
--- / t
2088 / 8
yes
type/litres
Polyolester (POE)/1.2
Litres
2.6
3~/N/PE 400 V (50 Hz) /
C10 A / A
1~/N/PE 230 V (50 Hz) /
4 AT
IP 24
Soft starter
Yes
A
21
1.7 / 3.3
kW
A / ---
3.1 / 0.8
70 / thermostatically
W
controlled
W
up to 100
9
Reverse circulation
Yes
bar
3.0
A++ / 172 %
LA 9S-TU(R) - LA 18S-TU(R)
LA 12S-TU
LA 18S-TU
Air
Universal
WPM Econ 5S, wall-
WPM Econ 5S, wall-
mounted
Outdoors
Integrated
Integrated
1
up to 60 ± 2 / from 18
up to 60 ± 2 / from 18
-22 to +35
-22 to +5
1.9 / 17800
1.5 / 10000
1.8 / 16800
1.4 / 8900
5
1.2
/ 6100
1.4
1.4 / 10000
1.4 / 8900
54 / 53
26 / 25
4700 / 3600
5500 / 3200
1650 x 910 x 750
1650 x 910 x 750
265
R410A / 4.78
R410A / 5.9
2088 / 9
yes
Polyolester (POE)/1.2
Polyolester (POE)/1.2
3.8
3~/N/PE 400 V (50 Hz) /
3~/N/PE 400 V (50 Hz) /
C10 A / A
1~/N/PE 230 V (50 Hz) /
1~/N/PE 230 V (50 Hz) /
4 AT
IP 24
Soft starter
Soft starter
Yes
19
2.38 / 4.0
4.3 / 0.8
70 / thermostatically
70 / thermostatically
controlled
controlled
up to 150
9
Reverse circulation
Reverse circulation
Yes
3.0
A++ / 167 %
A++ / ^179 %
www.glendimplex.de
Air
Universal
mounted
Outdoors
2
2
3
/ +35
5
/ 3700
54 / 53
26 / 25
295
2088 / 12
yes
3.8
C13 A / B
4 AT
IP 24
Yes
21
3.24 / 6.8
5.9 / 0.8
up to 200
9
Yes
3.0

Publicité

loading

Ce manuel est également adapté pour:

La 9s-turLa 12s-tuLa 12s-turLa 18s-tuLa 18s-tur