14.2.2) PROGRAMMING NOTES
Simultaneously pressing <+> and <-> from inside a function menu allows you to return to the previous menu without making any changes. Hold down
the <+> key or the <-> key to accelerate the increase/decrease of the values.
Hold down the <+> key or the <-> key to accelerate the increase/decrease of the values. After waiting 120s the control unit quits programming mode
and switches off the display. When the board is switched on, the software version is displayed for around 5 sec
The pre-set logic functions and parameters are made taking account of a typical installation.
14.3) PARAMETERS, LOGICS AND SPECIAL FUNCTIONS
The following tables describe the functions available on the control unit
MENU
Select the length of the boom installed on the barrier.
Value expressed in meter from 3m (DIVA.3) or from 5m (DIVA.5)
BOOM
According to the selected boom length, the optimal value of parameters:
FST0/FTSC/SLDO/SLDC/TSMO/TSMC//TACC/TDEC will be set.
Set the closing direction of the barrier (see fig. 3)
The symbol 0--- indicates right barrier (R/RIGHT) DEFAULT
Pos
The symbol ---0 indicates left barrier (L/LEFT)
Verify the opening direction of the boom and in case reverse it. Every change of this func-
tion automatically implies the starting of a new AUTOSET procedure.
Select the use mode of the barrier.
Norm: Standard operating mode, for barriers used in a residential/industrial environment and
with normal traffic.
Parc: Park operating mode, for barriers used in parking systems. In this mode, to promote
transit of a high number of vehicles, the control unit automatically sets a specific configuration
Mode
which includes:
1) Rapid closure enabled (SCL:ON) with time reduced from 3 to 0 seconds.
2) Automatic closure enabled (TCA:ON) which with rapid closure enabled causes, during the
opening phase, immediate closure of the barrier as soon as the PHOT input is free.
3) During the closure phase, PHOT entrance activation stops the barrier, as soon as the PHOT
input is free again, the barrier starts the closure manoeuvre.
MENU
Automatic closing time. Enabled only with logic "TCA"=ON.
TCA
At the end of the set time, the control unit commands a closing manoeuvre .
FST0
It adjusts the barrier opening speed (standard speed, before the slowing phase).
FSTc
It adjusts the barrier closure speed (standard speed, before the slowing phase).
sldo
Adjusts the slowdown speed of the barrier during the opening phase* (Fig.10) .
sldc
Adjusts the slowdown speed of the barrier during the closing phase* (Fig.11)
Sets the starting point of the slowdown during the opening phase (Fig.10).
tsmo
The value is expressed in percentage on the entire stroke.
Sets the starting point of the slowdown during the closing phase (Fig.11).
tsmc
The value is expressed in percentage on the entire stroke.
PMO
Adjusts the motor torque applied to the barrier during the opening phase (Fig.10 - FSTO).*
PMC
Adjusts the motor torque applied to the barrier during the closing phase (Fig.11 - FSTC).*
Adjusts the motor torque applied to the barrier during the slowdown in opening phase*
PSO
(Fig.10 - SLDO).
Adjusts the motor torque applied to the barrier during the slowdown in closing phase*
PSC
(Fig.11 - SLDC). .
It adjusts the time the barrier takes to go from stop status (in opening or closure) to the speed
TACC
set by the FSTC/FSTO parameters.
Value expressed in tenths of a second.
It adjusts the time the barrier takes to go from the speed set by the FSTC/FSTO parameters (in
TDEC
opening or closure) to the speed of the slowing phase SLDO/SLDC.
Value expressed in tenths of a second.
Adjusts the intervention threshold of the anti crushing device (Encoder) during the normal speed*.
SeaU
0:Off -1: minimum sensitivity - 99: maximum sensitivity
Adjusts the intervention threshold of the anti crushing device (Encoder) during the slowdown
SEAR
speed*.
0:Off -1: minimum sensitivity - 99: maximum sensitivity
14.3.1) INSTALLATION (INST)
FUNCTION
14.3.2) PARAMETERS (PAR)
FUNCTION
MIN-MAX-(Default)
MEMO
3 -5 (5)
= RIGHT
0---
= LEFT
---0
( RIGHT )
Norm - Parc (Norm)
MIN-MAX-(Default)
MEMO
30-80-(50)
30-80-(50)
30-80-(50)
10-30-(15)
10-30-(15)
20-99-(40)
20-99-(40)
1-99-(10)
1-99-(10)
1-99-(10)
1-99-(10)
3-50 (15)
3-30 (20)
0-99-(0%)
0-99-(0%)
EN
27