- De-excitation time
- Codes in store
- All the inputs must be used as clean contacts because the power supply is generated
internally (safe voltage) in the card and it is set in a way to guarantee the use of the double
insulation and reinforced in relation to parts with hazardous voltage.
- Any external circuits connected to the outputs of the control board, must be carried out to
make sure the double or reinforced insulation is used in relation to parts with hazardous
voltage.
- All the inputs are run by a programmed integrated circuit which carries out a self-check at
the beginning of each operation.
MAINTENANCE CHECK
N.B.: During this check the safety functions Edges, Photocells, Stop button and Impact
detection are NOT active.
1 - Set DIP 1 to ON => LED DL1 starts to flash.
2 - Press and hold the PROG button (the command is hold-to-run, open-stop-close-stop-
open-etc ...) => The gate starts at high speed and then slow down until the limit switch
is reached.
3 - At the end, put DIP 1 back to the OFF position. The DL1 LED turn off signaling the exit
from the check.
If the motor does not work during this check, check the connections and its capacitor.
If the motor is working properly, check the safety devices.
FINAL OPERATION -
Fit the gasket
300ms
N° 1000 total
The gasket shall be fitted only at the end of the installation, before you mount the case.
The gasket is fitted
TROUBLE SHOOTING
After having carried out all connections, by carefully following the layout and having
positioned the gate in intermediate position, check the correct ignition of red LEDS DL6, DL7,
DL8, DL9 and DL10.
In case of no ignition of the LEDS, always with gate in intermediate position, check the
following and replace any faulty components.
DL6
OFF
the jump between COM A+ and STOP).
DL7 or DL8
OFF
out jumper between COM A+ and PHOTO 1/PHOTO 2)
DL9 or DL10
OFF
out jumper between COM A+ and EDGE 1/EDGE 2)
LED DL13 (BLUE)
ON
smartphone check the card functions as the dips/trimmers status may not be true.
On the board there are resettable fuses which intervene in the event of a short circuit,
interrupting the output assigned to them.
In the event of troubleshooting, it is advisable to disconnect all the removable
connectors and insert them one at a time in order to more easily identify the cause
of the fault.
Close the case
37
Stop button malfunction (if Stop is not connected, perform
Faulty photocells (In case the edge is not connected, carry
Faulty safety edge (In case the edge is not connected, carry
Some functions are enabled via smartphone, so via
Motor ready
G
B