Télécharger Imprimer la page

BIEMMEDUE GA/N 115C Manuel D'instructions page 60

Masquer les pouces Voir aussi pour GA/N 115C:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 23
Warning
All of the operations described in this section must be performed by professionally qualified personnel only.
5.1. INSTALLATION ON FLOOR OR CEILING
The space heater can be installed on a support base, which must be:
• stable and horizontal
• made of non-combustible material
Accessories include support hooks to suspend the heater by hooking it to the ceiling with ropes and/or chains of
appropriate capacity and length, to be attached to the four suspension points
Warning
Make sure that the ropes and/or chains form an angle not more than 5° with vertical to the ceiling, that the
ropes do not cross, and that a different rope is used for each hook.
The minimum distance from surrounding walls, floor and/or ceiling must be at least 1 m and the distance from the
floor of at least 500 mm.
L-L 337.00-BM
EN
5. INSTALLATION INSTRUCTIONS
NO
60 / 116

Publicité

loading