Télécharger Imprimer la page

TDK-Lambda RFE1000 Serie Instructions D'installation page 13

Publicité

RFE 1000 SERIES INSTRUCTION MANUAL
RFE1000 SERIES SPECIFICATIONS
Rated output voltage
1
Output voltage set point
2
Output voltage range
3
Maximum Output Current (Refer to Fig.1)
4
Maximum output power
5
Input voltage / frequency range
6
Maximum input current (at 100/200Vac)
7
Power Factor (Typ)
8
Efficiency (Typ)
9
Inrush current
10
Hold-up time
11
Maximum line regulation
12
Max load regulation
13
Output Ripple and noise
14
Temperature stability
15
Temperature coefficient
16
Remote sensing
17
Parallel operation
18
Series operation
19
Over current protection
20
Over voltage protection
21
Over temperature protection
22
Remote OnlOff control
23
DC OK signal
24
Over-Temp. warning
25
AC fail signal
26
Auxiliary power supply
27
Vout voltage trimming
28
Output indicator
29
Operating temperature
30
Storage temperature
31
Operating humidity
32
Storage humidity
33
Cooling
34
Vibration
3S
Shock
36
Conducted emission
37
Radiated emission
38
Applicable safety standards
39
Withstand voltage
40
Insulation resistance
41
Leakage current
42
Weight (Typ)
43
Size (W*H*D)
44
Notes:
*1: For cases where conformance to various safety standards (UL, EN etc.) is required.
to be described as 100-240Vac (50/60Hz).
*2: At 100/200Vac, rated load and 25°C ambient temperature.
*3: Not applicable for the noise filter inrush current less than 0.2mS.
*4: Measured with JEITA RC-9131A 1:1 probe, 20MHz B.W.
*5: From 85-132Vac or 170-265Vac, constant load.
*6: From No-load to Rated load, constant input voltage. Measured at Ihe sensing point in Remote sense.
*7: Remote sensing can compensate up to 1V drop on each load wire.
*8: Inverter shut down method. Reset by AC voltage recycle or by On/Off control.
*9: Derate Maximum output power by 10% for input voltage less than 95VRMS
Model
RFE1000 -24
V/I
V1 (V)
24
V2 (V)
29
I1 (A)
33
I2 (A)
40
RFE1000-24
V
24
V
24+/-1%
V
21.5-29
A
40
(*9)
W
960
(*1)
-
A
-
(*2)
%
86/88%
(*3)
A
mS
20mS typical at 100Vac input, rated output voltage and less than 80% of rated load
(*5)
-
(*6)
-
(*4)
mV
200
-
0.1 % of rated Vout for 8hrs after 30mln warm-up. Constant line. load and temperature.
PPM/°C
(*7)
V
-
-
-
105--125% of maximum oulool current. Refer to Fia. 1
(*8)
V
31-34
-
-
By electrical signal or dry contact. ON: 0~0.6V or short. OFF: 2~15V or open.
-
Open collector signal. On when Vout>80+/-5% rated output. Max.sink current: 10mA
-
-
-
-
-
-
0....50°C: 100% load. Derate 2%/°C. 50°C to 60°C. Derate 2.5%/°C. 60°C to 70°C.
-
-
-
-
-
-
-
-
-
Input-Output: 3000Vrms,1min. Input-Ground: 2000Vrms. 1min. Output-Ground: 500Vrms, 1min.
-
-
More than 100Mohm at 25°C and 70% RH. Output-Ground: 500Vdc
mA
Kg
-
RFE1000 -32
RFE1000 -48
32
48
38.4
58
26
17.25
31
21
RFE1000-32
32
32+/-1%
28.8-38.4
31
992
85~265Vac continuous, 47~63Hz, Single phase
12.0/6.0
>0.98 at 115/230V and maximum output power
86/88%
Less than 40A
0.40%
0.80%
250
200
Possible. Refer to Instruction Manual.
Possible. Refer to Instruction Manual.
Possible. Refer to Instruction Manual.
41.5-45.5
Inverter shut down method, automatic reset.
Open collector signal. Refer to Instruction Manual
Open collector signal. Refer to Instruction Manual
11.2~12.5VDC. 0.25A Maximum output current.
User accessible Internal Potentiometer. Full range.
Green LED DC OK
-30....85°C
10-90% RH, no condensation.
10-95% RH, no condensation.
By internal Fans. Variable speed control.
Built to meet ETS 300 019
Built to meet ETS 300 019
EN55022B FCC part 15J-B VCCI-B
EN55022B, FCC part 15J-B, VCCI-B
UL60950-1, EN60950-1
Less Than 1.1 mA at 230Vac
2.0
127x41 x305 mm. Refer to Outline Drawing.
Vout (V)
V2
V1
I1
Fig. 1: Rated output current vs output voltage
RFE1000-48
48
48+/-1%
43-58
21
1008
87/89%
300
62-66
Iout (A)
I2

Publicité

loading