8. TECHNICAL DATA
MultiPlus
PowerControl / PowerAssist
Transfer switch (A)
Minimum PowerAssist current (A)
INVERTER
Input voltage range (V DC)
Output
Cont. output power at 25 °C (VA) (5)
Cont. output power at 25 °C (W)
Cont. output power at 40 °C (W)
Peak power (W)
Maximum efficiency (%)
Zero-load power (W)
Zero load power in search mode (W)
CHARGER
AC Input
Charge voltage 'absorption' (V DC)
Charge voltage 'float' (V DC)
Storage mode (V DC)
Charge current house battery (A) (4)
Charge current starter battery (A)
Battery temperature sensor
GENERAL
Multi purpose relay (6)
Protection (2)
Common Characteristics
ENCLOSURE
Common Characteristics
Battery-connection
230 V AC-connection
Weight (kg)
Dimensions (hxwxd in mm)
STANDARDS
Safety
Emission / Immunity
12/2000/80-30
24/2000/50-30
230V
Yes
30
2,7
9,5 – 17
Output voltage: 230 VAC ± 2%
Frequency: 50 Hz ± 0,1% (1)
2000
1600
1450
3500
93
10
3
Input voltage range: 187-265 VAC
Input frequency: 45 – 65 Hz
14,4 / 28,8
13,8 / 27,6
13,2 / 26,4
80
Operating temp. range: -20 to +50° C (fan assisted
cooling) Humidity (non condensing) : max 95%
Material & Colour: aluminium (blue RAL 5012)
Protection category: IP 21
Bolts M8
WAGO CAGE CLAMP® connector
520 x 255 x 125
EN 60335-1, EN 60335-2-29
EN55014-1, EN 55014-2, EN 61000-3-3
230V
Yes
30
2,7
19 – 33
2000
1600
1450
4000
94
10
3
Power factor: 1
28,8
27,6
26,4
50
4
yes
yes
a - g
6 mm², 10 AWG
12
25

Publicité

loading

Ce manuel est également adapté pour:

Multiplus 24/2000/50-30 230v