Télécharger Imprimer la page

Victron energy MultiPlus 12/2000/80-30 230V Manuel page 25

Publicité

Les langues disponibles
  • FR

Les langues disponibles

ds3-ds4: Setting charge voltages
Absorption
ds3-ds4
voltage
dS3=off
14.4
dS4=off
28.8
(default)
57.6
dS3=on
14.1
dS4=off
28.2
56.4
dS3=off
14.7
dS4=on
29.4
58.8
dS3=on
15.0
dS4=on
30.0
60.0
Batteries with high antimony content can typically be charged with a lower absorption
voltage than batteries with low antimony content. (Please refer to our book "Electricity
on Board" downloadable from our website
suggestions about charging batteries). Contact your battery supplier for the correct
charge voltages and change (with VE-configure) the voltage settings if required.
The default charge current setting is 75% of the maximum charge current. This current
will be too high for most applications.
For most battery types the optimal charge current is 0.1-0.2x the battery capacity.
ds5: Inverter frequency
ds6: Search Mode
ds7: AC input current limit
Store the settings by moving Dip switch 8 to "on" and back to "off".
Float
Storage
voltage
Voltage
13.8
13.2
27.6
26.4
55.2
52.8
13.8
13.2
27.6
26.4
55.2
52.8
13.8
13.2
27.6
26.4
55.2
52.8
13.8
13.2
27.6
26.4
55.2
52.8
www.victronenergy.com
off = 50Hz
off = off
off = 16 Amp
Absorption
Time
Suitable for
(hours)
Gel Victron Deep
Discharge
8
Gel Exide A200
AGM Victron Deep
Discharge
Gel Victron Long
Life (OPzV)
8
Gel Exide A600
(OPzV)
Gel MK battery
AGM Victron Deep
Discharge
Tubular plate or
5
OPzS batteries in
semi-float mode
AGM spiral cell
Tubular plate or
6
OPzS batteries in
cyclic mode
on = 60Hz
on = on
on = 30 Amp
for details and
21

Publicité

loading

Ce manuel est également adapté pour:

Multiplus 24/2000/50-30 230v