LED Display
Definition
F1
Encoder/ Limit switch
F2
Number of operators
F3
Maximum trapping force
F4
Gate speed
F5
Slowdown
F6
Soft stop speed
F7
Lapse between leaves in
opening and closing
F8
Semi-automatic or
automatic
operation mode and
stand-by
time (in seconds) in
automatic
mode
F9
Photocell Function mode
(Open-close,
interior-exterior)
FA
Pedestrian opening
FB
Flashing light pre-warning
¡ ATTENTION ! The 24Vdc flash light output is not fixed output but flashing. To connect a fixed or a fixed mode flash
light for the proper Function.
NOTE (Parameter F9)
Exterior Photocell: Only be activated in case of door closing.
Interior Photocell: Can be activated in door opening and door closing..
Complete programming chart (1)
Parameter
Mode
F1-1
Motor only
F1-2
Motor with limit switch
F1-3
Motor with encoder
F2-1
Two Operators
F2-2
One Operator
F3-1
2A
F3-2
3A
F3-3
4A
F3-4
5A
F4-1
100% Full Speed
F4-2
80% Full Speed
F5-1
Function ON
F5-2
Function OFF
F6-1
70% Full Speed
F6-2
50% Full Speed
F6-3
35% Full Speed
F6-4
25% Full Speed
F7-1
2 sec.
F7-2
3 sec.
F7-3
4 sec.
F7-4
5 sec.
F7-5
6 sec.
F7-6
7 sec.
F7-7
8 sec.
F7-8
9 sec.
F7-9
10 sec.
F8-0
OFF
F8-1
3 sec.
F8-2
10 sec.
F8-3
20 sec.
F8-4
40 sec.
F8-5
60 sec.
F8-6
120 sec.
F8-7
180 sec.
F8-8
300 sec.
F9-1
Mode 1
F9-2
Mode 2
F9-3
Mode 3
F9-4
Mode 4
FA-0
OFF
ON
FA-1
FB-0
OFF
FB-1
On
Description
1. The factory setting is "F1-1".
1. The factory setting is "F2-1".
1. The factory setting is "F3-1".
2. Please make sure that the parameter F3 is always in F3-1
in case of system learning process.
1. The factory setting is "F4-1".
1. The factory setting is "F5-1".
1. The factory setting is "F6-2".
1. The factory setting is "F7-1".
1. The factory setting is "F8-0".
1. The factory setting is "F9-1".
Mode 1: Photocell Exterior FT1- Photocell Interior FT2
Mode 2: Photocell Exterior FT1- Safety Belt FT2
Mode3: Photocell Exterior FT1- Open Device FT2
Mode 4: Photocell Interlock FT1- Fotocélula Interior FT2
1. When Function on and push B key in the transmitter, one
gate will open partically.
2. The factory setting is "FA-0".
1. When Function ON, the light will flash before the gate
operate 3 seconds. If set OFF, the flash light will operate
with motor in the same time.
2. The factory setting is "FB-0".
7