DIP 6 ON => The K BUTT, the PED BUTT button, the RADIO REMOTE buttons perform the cyclic
command open-stop-close-open-stop-etc.
DIP 6 OFF => The K BUTT, the PED BUTT button, the RADIO REMOTE buttons perform:
- the open command, if pressed with the gate completely closed
- the close command, if pressed with the gate completely opened
- no effect, if pressed during the gate opening
- the gate re-open, if pressed while the gate is closing
The K BUTT opens the gate completely, whereas the PED BUTT opens the gate partially as
described in Point D.
CLOCK FUNCTION
If you want the Clock Function must request K with firmware 12 NOUP.
ATTENTION: A CLOCK CONNECTED TO K with fw 05 or more ACTIVATES THE AUTOMATIC
MOVEMENT OF THE GATE WITHOUT HAVING THE PROTECTION OF THE SAFETY DEVICES!
The Clock Function is useful during rush hours, when traffic is heavy and the flow is slow (e.g.
entrance/exit of employees, emergencies in residential areas or car parks and, temporarily, for
removal vans) and it's necessary to keep the gate opened.
CLOCK FUNCTION APPLICATION
It is necessary to request a K control panel with firmware 12 NOUP.
Select the automatic functioning DIP 6 OFF.
It can be done by connecting a switch and/or a daily/weekly clock either in parallel to the K
BUTT button or instead of the K BUTT button. When the control board receives this command,
the gate will open and by keeping this contact closed for all the time of the gate opening, the
Clock Function is automatically activated. In fact, once reached the open position, the gate will
remain opened and all of the control board functions are blocked. Only when K BUTT contact is
released, the control board functions are re-activated and the Automatic Closing restarts (if
enabled) doing the countdown to the gate closing.
PEDESTRIAN command (PED BUTT - COM)
This command is useful to open the gate partially, just enough, for example, to permit a
pedestrian crossing. In fact, the Pedestrian command (see Point E) is carried out only by
opening the gate just enough for a pedestrian to pass, as described into the Point E procedure.
From the Pedestrian opening position the Automatic Closing can be enabled or disabled with
DIP 3.
From the Pedestrian opening position, the gate can be completely opened by the OPEN or by the
K BUTT button or by the RADIO button.
AUTOMATIC CLOSING (from the COMPLETE open position)
The Automatic Closing from the complete open position can be enabled turning ON the DIP 3.
The maximum gap of time that can be programmed is 5 minutes (see Point D).
AUTOMATIC CLOSING (from the PEDESTRIAN open position)
The Automatic Closing from the pedestrian open position can be enabled turning ON the DIP 3.
The maximum gap of time that can be programmed is 5 minutes (see Point E).
FUNCTIONING OF SAFETY ACCESSORIES
PHOTOCELL (PHOT - COM) - Safety function - PL "b" according to EN13849-1
DIP 4 OFF => the photocells are active both in gate opening and in gate closing. In this
configuration, if an obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will stop and will restart opening when the obstacle is
removed
- while the gate is still, it will not move neither in opening nor in closing.
DIP 4 ON => the photocells are active only in gate closing.
In this configuration, if an obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will continue open
- while the gate is still, it will open if a open command is request, it will remain still if a close
command is request.
The photocell input (PHOT - COM) is a NORMALLY CLOSED contact.
In case there are more couple of photocells, the contacts from all the photocell receivers must
be connected in series.
In case the photocells are not installed, this contact must be short circuited with a wire jump
(from PHOT to COM) to permit the gate to operate.
ATTENTION: In case the receiver led remains lit, malfunctioning of the main supply is
suspected.
It is advisable to connect electrically to earth the columns
or the photocells stands to the terminal A -, to shield the
photocells from external noise.
Be careful not to short circuit the system when the supply phases are inverted!
SAFETY STRIP (EDGE - COM) - Safety function - PL "b" according to EN13849-1
If it intervenes during opening, it inverts the movement and closes for 2 s and then stops.
If it intervenes during closing, it inverts the movement and opens for 2 s and then stops.
If the safety strip remains engaged (NO contact), no automatic movement is allowed.
In case the safety strip is not installed, this contact must be short circuited with a wire jump
(from EDGE to COM) to permit the gate to operate.
PAY ATTENTION: it is highly recommended to check safety-strips operation at least every 6
SAFETY STRIP ALARM
After the inversion given by the intervention of the safety edge, the gate stops in alarm mode
and this is signaled by the blinker on for 1 minute and by the buzzer on for 5 minutes.
During or after the minute of alarm, the normal gate operations can be restored by pressing
any push button.
TESTING THE SAFETY STRIP equipment
The DIP 10 ON enables to test the safety strip equipment. The test is performed every time the
gate completes a full opening. The test is available only if the safety strip device is equipped
with a dedicated power supply input.In fact, the safety strip equipment power supply input
can be connected to the A+TEST and A- outputs (DIP 10 ON). Automatically, every time the gate
completes a full opening, just before closing, the control board switches OFF the A+TEST and
A- power supply output for a very short time. While the safety strip power supply is switched
OFF, if everything is working fine the safety strip contact (EDGE - COM) must open. In case the
test fails, no other gate manoeuvre will be allowed and the alarm state will be signalled by both
the Blinker and the Buzzer, if installed, which will remain on for 5 minutes
NOT ALL THE SAFETY STRIPS CAN BE TESTED, THUS THE SWITCH DIP 10 MUST BE LEFT OFF.
STOP BUTTON - Safety function - PL "b" according to EN13849-1
If the Automatic command is enabled (DIP 6 OFF), a Normally Closed contact could be
connected in series to the COM wire of the opened and the closed limit switches.
This contact works like a STOP button to interrupt any gate manouver.
FUNCTIONING IN DEAD MAN MODE WHEN THE SAFETY DEVICES ARE FAILING
If the safety edge fails or remains engaged for more than 5 s, or if photocell fails or remain
engaded for more than 60 seconds, the K BUTTON and PEDESTRIAN commands will work only
in dead man mode.
The signal that this mode has been activated is given by the blinking of the programming led.
With the blinking of the programming led, the opening and closing operation are allowed only
with the command button pressed and held. The radio commands and that of automatic
closing, will be excluded, since their use in this mode, is not allowed by the norms.
Once the failing safety device is repaired, in automatic after 1 second, all standard commands
that were selected, such as step by step, automatic mode, radio commands and automatic
closing start functioning again.
Note 1: during this functioning in dead man mode, in case of damage to the safety strips (or
photocells) the photocells (or safety strips) still work by interrupting the operation
in progress.
The dead-man operation is only an emergency operation which must be activated for a very
short period and with the complete installation at sight so to have a secure and safe control
of the system. As soon as possible however, the failing safety devices must be repaired and
activated.
FLASHING LIGHT
Connect the flashing light to J7 flashing light outputs, use flashing lights (ACG7072) of 40 W
maximum.
NB: This control board can only supply power to FLASHING LIGHTS with inbuilt flashing circuit.
PRE-FLASHING function
DIP 5 ON => enables the pre-flashing, the FLASHING LIGHT and BUZZER starts working 3 seconds
before every movement of the gate.
DIP 5 OFF => disables any pre-flashing, the FLASHING LIGHT, the BUZZER and the motor will start
at the same time.
BUZZER (COM.+ BUZZER-)
The current supplied to the Buzzer will be 200 mA at 24 Vdc.
During the normal operation of the gate, opening and closing, the buzzer will buzz intermittently.
Only during the alarm situations (safety strip) the buzzing will almost be constant.
GATE OPEN INDICATOR (A negativo - LSC) - 3 W max
24 Vdc
It is turned ON when the gate is open or partially open, it is turned OFF only when the gate is
Term.
completely closed.
A -
N.B.: connect in series to the indicator a resistance of 2K2. WE RECOMMEND NOT TO OVERLOAD