Hazard information
Exceeding this capacity could lead to the destruction of the device,
fires or electric shocks.
The circuit to which the device and the load will be connected must
be protected by a circuit breaker in accordance with EN60898-1
(tripping characteristic B or C, max. 10 A rated current, min. 6 kA
breaking capacity, energy limitation class 3). Installation regulations
according to VDE 0100 and HD382 or 60364 must be observed. The
circuit breaker must be easily accessible to the user and marked as
the disconnecting device for the actuator.
Before the actuator is connected, remove the fuse from the fuse
box.
Except for configuration, the device may only be operated with an
associated switch cover.
The device has not been designed to support safety disconnection.
Only shutters and blinds with limit switches (mechanical or electro-
nic) should be used. Before putting the actuator into operation,
check that the limit switches on the connected motors have been
adjusted correctly.
The device must only be operated within residential buildings.
Using the device for any purpose other than that described in this
operating manual does not fall within the scope of intended use and
will invalidate any warranty or liability.
If used in a security application, the device has to be operated in
connection with an UPS (uninterruptible power supply) to bridge
possible power failure according to EN 50130-4.