6.4 PV Connection
Please ensure the follows before connecting PV strings to the inverter:
•
Make sure the open voltage of the PV strings will not exceed the max. DC input voltage (580
VDC). Violating this condition will void the warranty.
•
Make sure the polarity of the PV connectors is correct.
•
Make sure the PV-switch, breakers of battery, AC-BACKUP and AC-Grid are all in their off-
states
•
Make sure the PV resistance to ground is higher than 200 kΩ.
The inverter includes Staubli MC4 PV connectors.
Please follow the picture below to assemble the PV connectors.
PV conductor cross section requirements: 4-6mm²
1. Strip off the insulation.
PV1-F/UL-ZKLA/USE2
PV1-F/UL-ZKLA/USE2
3. Assemble the connectors.
2.6-2.9Nm
Please check if the cables are securely installed by
pulling outwards.
© 2023 Maxeon Solar Technologies, Ltd. All rights reserved. | 547143 Revision B - June 2023
Specifications included in this document are subject to change without notice
7mm
7mm
4-6mm²
Positive
Negative
2. Assemble the MC4 cable ends.
Crimp pliers to cable ends.
Positive terminal
Negative terminal
Crimp pliers to
cable ends
4. Check the polarities of the PV strings. Check
the open-circuit voltage is less than 580V.
39