2
Maximum load for each single output:
X31 Relays Outputs
250 VAC, max. 3 A G.P.
(OUT 5,
OUT 6,
30 VDC, 3 A G.P.
C300, R150 (Pilot Duty)
OUT 7,
OUT 8)
Maximum total load at all four outputs:
250 VAC, max. 3 A G.P.
30 VDC, 3 A G.P.
120 / 240 VAC, 180 VA (Pilot Duty)
125 / 250 VDC, 28 VA (Pilot Duty)
2
Maximum load for each single output:
X32 Relays Outputs
(OUT 9,
250 VAC, max. 3 A G.P.
30 VDC, 3 A G.P.
OUT 10)
C300, R150 (Pilot Duty)
2
The relay terminals X31 and X32 can be connected either to the mains
voltage, low voltage or class 2 circuits. Mixing different voltage circuits within
one terminal is not permitted.
The changeover contacts (OUT9/OUT10) on terminal X32 are also intended for
connection to the same voltage circuits. The connection of different voltage
circuits is not permitted For voltages above 150 V, it is necessary that the
"COMMON" terminals of OUT9 and OUT10 have the same voltage potential.
NOTE
The interconnection of Class 2 outputs is prohibited.
Cable size
Connection
2
AWG
(mm
)
X31
310-319
(0.2 – 3.3)
24 - 12
X32
320-325
X33
330-335
(0.2 – 3.3)
X34
340-342
24 - 12
X36
360-363
X38
380-385
(0.2 – 1.3)
24 - 16
X39
390-393
In the field-wiring area, provisions for wiring for Class 2 and Class 3 circuits must
meet the requirements for separation from Class 1 circuits in accordance with
Section 725 of the National Electrical Code, ANSI/NFPA 70 and Section 16 of the
Canadian Electrical Code. Separation from power and lighting circuits is required
for Class 2 by one of the following means:
a)
A permanent barrier shall be provided to separate the field installed Class 2
conductors of secondary circuits from all other circuits or;
b)
Provisions need to be made to route the Class 1 or power circuit conductors
in order to maintain a minimum 1/4-in (6.35 mm) separation from the
conductors of the Class 2 circuits.
E-File No. E218753
Controller
4.6
Assembly and connection
DANGER
Risk of electric shock!
Before connecting the accessories, switch off the supply voltage of the
controller!
Do not switch on the supply voltage of the controller again until the
installation of the accessories has been completed, the controller is
covered and no live parts can be touched.
ATTENTION
Connect connection terminals before connecting to the plug connectors! Only
thus is it possible to ensure a safe contact of the connection terminals to the
plug connectors.
NOTE
Use only 75 °C copper cable to connect to the expansion board.
The description of the connection to the controller can be found in the
assembly instructions of the respective controller.
Required tools: Cross screwdriver PH 1, slotted screwdriver size 0.6 x 3.5 and
0.4 x 2.5
4.7
Mounting for the TSTFUZ2 Series
Tightening
See "Für TST FUZ2 Serie/For TST FUZ2 Series/Pour Série TST FUZ2", figure on
torque
NEC wiring
page 1.
Lb-in
[NM]
TST FUZ2-B:
1. Attach the 3 spacers C to the real text display using the 3 screws B.
3.5
(0.4)
Class 1
2. Connect the connection cable E to the connection X40.
3. Connect the connection cable G to the connection X30a.
TST FUZ2-CX:
3.5
(0.4)
Class 2
1. Attach the 3 spacers D with the 3 screws B to the expansion board.
2. Connect the connection cable F to the connection X40.
3. Connect the connection cable H to the connection X30a.
2.2
(0.25)
Class 2
4. Connect the expansion board to the controller (see installation instructions for
the control unit, chapter "Connecting TST RFUxK/TST RFUxK2").
5. Activate the expansion board via the controller: Set parameter P.800 to 5.
TST RFUxK2-E
TST_RFUxK2-E_Install_rev4_mul
7 | 10
Lange Straße 4 | D-35781 Weilburg
Tel. +49 6471 3109-0 | Mail:
4.8
Mounting the TST FUF2, TST FU3F Series
See "Für TST FUF2, TST FU3F Serie/ For TST FUF2, TST FU3F Series/Pour
Série TST FUF2, TST FU3F", figure on page 2.
1. Attach the 3 spacers K with the 3 screws I to the expansion board.
2. Attach the fourth spacer K with the polyamide screw J to the expansion board.
3. Connect the connection cable L to the connection X40.
4. Connect the connection cable M to the connection X30a.
5. Connect the expansion board to the controller (see installation instructions for
the control unit, chapter "Connecting TST RFUxK/TST RFUxK2").
6. Activate the expansion board via the controller: Set parameter P.800 to 5.
4.9
Mounting the real text display TST KKTA
See " TST KKTA montieren/Mounting TST KKTA/Montage de la TST KKTA ",
figure on page 2.
1. Attach the 3 spacers O to the real text display using the 3 screws N.
2. Insert the spacers with the real text display into the openings of the expansion
board TST RFUxK.
FEIG ELECTRONIC GmbH
info@feig.de