OPERATING CYCLE
ARIA
Necessary input signals
Output signals
A
Begin start up
B
Flame present
B-C
Operation
C
Control stop
C-D
Air gate closure + post-purge
LME EQUIPMENT
The release pushbutton on the equipment is the main component for accessing all the diagnostic functions (activation and
deactivation) as well as for releasing the control and checking device. The release pushbutton has a multicoloured led
which indicates the state of the control and checking device during operation and when the diagnostic function is in use.
EQUIPMENT STATE INDICATORS
Description
Condition
Standby, other intermediate states
Ignition stage
Correct operation
Incorrect operation, current level of
flame detector below permitted minimum
Drop in voltage
Burner lock out
Fault (see table)
Stray light before burner ignition
Rapid flashing for diagnostics
TW
Begins with the closure of the thermostatic
line or the PG. The PA must be in the rest
position. This is the waiting and self-test
time lasting for 2,5 seconds.
T10
Begins when the motor starts up and with
the pre-purge phase; it lasts for 5 seconds,
within which the PA air pressure switch
must give the go-ahead.
T1
Pre-purge time, which lasts for at least 30
seconds, ending when the transformer star-
ts up.
T3
Pre-ignition phase, it ends when the gas
valve opens, and it lasts for 2 seconds.
T2
Safety time, within which the flame signal
must reach the EC electrode; it lasts for 3
seconds.
TC-PG
Thermostats/Gas pressure switch line
MB
Burner motor
PA
Air pressure switch
TR
Ignition transformer
V
Gas valve
EC
Control electrode
Colour sequence
No light
Yellow, flashing
Green
Green, flashing
Alternating yellow red
Red
Red, flashing
Alternating green red
Red, rapid flashing
- 31
-