2. OUTDOOR UNIT INSTALLATION
2-1. INSTALLING THE UNIT
• Be sure to fix the unit's legs with bolts when installing it.
• Be sure to install the unit firmly to ensure that it does not fall by an earthquake or a gust.
• Refer to the figure in the right for concrete foundation.
• Do not use the drain socket and the drain caps in the cold region. Drain may freeze and it makes the fan stop.
Make the setting
depth deeper.
2-2. CONNECTING WIRES FOR OUTDOOR UNIT
• Be sure to use special circuits for room air conditioner.
• Wiring work should be based on applicable technical standards.
• Wiring connections should be made following the diagram.
• Screws should be tightened so they won't loosen.
1) Remove the service panel.
2) Remove the conduit plate.
3) Attach the conduit connector to conduit plate with lock nut then secure
it to the unit with screws.
4) Connect ground wires to the TB support.
5) Loosen terminal screw, and connect indoor/outdoor unit connecting
wire (B) from the indoor unit correctly on the terminal block. Be careful
not to make mis-wiring. Fix the wire to the terminal block securely so
that no part of its core is appeared, and no external force is conveyed
to the connecting section of the terminal block.
6) Firmly tighten the terminal screws to prevent them from loosening. After
tightening, pull the wires lightly to confirm that they do not move.
7) Perform 5) and 6) for each indoor unit.
8) Connect power supply cord (A).
9) Close the service panel securely. Make sure that 3-3. PIPE CONNEC-
TION is completed.
Connecting order
• Connect the terminal block in
following order.
A → B → C → D → P
D unit is for 4C36NA4 only
Remark:
* A disconnect switch should be required. Check the local code.
** Use a ring tongue terminal in order to connect a ground wire to terminal.
INDOOR UNIT
A – C D
Terminal block
Grounding
terminal **
208/230 VAC
1 phase 60 Hz
Disconnect
switch *
Grounding
terminal **
Terminal block
A – C D
D unit is for 4C36NA4 only
Fix here with
M10 bolts.
Make with wider.
Power supply
Terminal block for
indoor/outdoor unit
5/8 in.
1-3/8 in.
(15 mm)
(35 mm)
Terminal block
Lead wire
Power supply
208/230 VAC
1 phase 2 wires 60 Hz
Grounding
terminal **
Terminal block
Terminal block 1
OUTDOOR UNIT
23-5/8
Anchor leg
Anchor bolt length
Anchor bolt pitch
ELECTRICAL SPECIFICATIONS
OUTDOOR UNIT
MXZ-3C24NA4
Power supply (V, PHASE, Hz)
Max. Fuse size (time delay) (A)
Min. Circuit Ampacity (A)
Fan motor (F.L.A)
(R.L.A)
Compressor
(L.R.A)
Indoor unit-Remote controller : (Wireless)
Control voltage
Indoor unit-Outdoor unit : DC12-24V
Screws
Service panel
• Connect wires to the matching numbers of terminals.
• Be sure to attach each screw to its correspondent terminal when
securing the cord and/or the wire to the terminal block.
CONNECTING WIRES AND CONNECTING GROUND WIRE
• Use solid conductor Min. AWG14 or stranded conductor Min. AWG14.
• Use double insulated copper wire with 600 V insulation.
• Use copper conductors only.
* Follow local electrical code.
POWER SUPPLY CABLE AND GROUND WIRE
• Use solid or stranded conductor Min. AWG12.
• Use copper conductors only.
* Follow local electrical code.
WARNING:
Use the indoor/outdoor unit connecting wire that meets the Standards
to connect the indoor and outdoor units and fix the wire to the terminal
block securely so that no external force is conveyed to the connecting
Ground
section of the terminal block. An incomplete connection or fixing of the
wire could result in a fire.
For future servicing, give extra length to the connecting wires.
(600)
(Unit: inch (mm))
MXZ-3C30NA4
MXZ-4C36NA4
208/230, 1, 60
25
22.1
2.43
12
13.7
Conduit plate
Conduit connector
Lock nut
Conduit plate
23.1
2.43
12
13.7
en-4