DIP-SWITCH SETTINGS

Dip_Board
Position
On
Dip1
Off
On
Dip2
Off
On
Dip3
Off
On
Dip4
Off
On
Dip5
Off
On
Dip6
Off

AUTOTEST FUNCTION

This function is designed to check the opera-
tion of the fan, valves and heaters.
To run the Autotest function, proceed as fol-
lows:
1) Selector switch B in central position.
2) Selector switch A in OFF position.
3) Adjust the selector switch A rapidly to obtain
the following sequence:
AUTO → OFF → V1 → OFF → V2 → OFF →
V3 → OFF.
At this stage the unit sets to AUTOTEST mode
(PINK LED flashing).
4) With the selector switch A in the AUTO posi-
14
Meaning
Cut-off valve present
Cut-off valve absent
Water probe upstream of the 3-way valve
Water probe downstream of the 3-way valve
Air probe correction present
Air probe correction not present
AUX position: plasmacluster control as purification system only
AUX position: SLEEP function
Dead zone 2°C
Dead zone 5°C
MS input with season changeover function
MS input with fan coil enabling function
B
-
A
OFF
ON
tion, the valve is activated. Yellow LED
(D) runs 1-flash cycles.
5) With the selector switch A in the V1
position, minimum speed V1 is activa-
ted. Yellow LED (D) runs 2-flash cycles.
+
6) With the selector switch A in the V2
position, the medium speed V2 is activa-
ted. Yellow LED (D) runs 3-flash cycles.
7) With the selector switch A in the V3
position, the maximum speed V3 is acti-
vated. Yellow LED (D) runs 4-flash cycles.
The Autotest function automatically
stops after one minute.