Quick Installation
Optional Hardwire Input
(Select models only. Proceed to Step
Hardwire Warnings
• Wiring must be performed by a qualified electrician.
• A readily visible and adequate disconnect device must be
provided.
• Make sure that your equipment is properly grounded.
• When making wiring connections, observe local/national
cable connection regulations at all times. Ensure that cables
are fitted with cable sleeves and secured by connector
clamps.
• Using cables of improper size may damage your equipment and
cause fire hazards. Choose appropriate cabling and protection
circuits to make wiring connections. (Ground conductors
must be the same size and type as power conductors.)
• Overcurrent protection should be provided per local/national
electrical codes.
3A
Select models have an optional hardwire input that can be
connected by a qualified electrician. While the UPS
system is turned OFF and unplugged, remove the input
power cord
, the input power cord panel
A
adjacent wiring access panel
3B
The input terminal block should be wired directly to a
dedicated AC supply circuit rated in accordance with the
specifications listed on the UPS system nameplate. The
hardwire input panel
the input power cord panel. (Note: The hardwire input
panel has a larger cutout that accommodates conduit.)
After threading user-supplied input wiring through user-
supplied conduit, insert the conduit through the hardwire
input panel and connect the input wiring to the input
terminal block. The terminals are labeled " " for
ground, "N" for neutral and "H" for hot. Connect the
input hot wire to the input hot terminal
input neutral wire to the input neutral terminal
Connect the input ground wire to the ground terminal
3C
After connecting the input wiring to the terminal block, secure
the wiring access panel
4
Plug your equipment into the UPS.*
* Your UPS is designed to support only electronic equipment. You will
overload the UPS if the total VA ratings for all the equipment you
connect exceeds the UPS's Output Capacity. To find your equipment's
VA ratings, look on their nameplates. If the equipment is listed in amps,
multiply the number of amps by 120 to determine VA. (Example: 1 amp
× 120 = 120 VA). If you are unsure if you have overloaded the UPS's
outlets, see "OUTPUT LOAD LEVEL" LED description.
Turn the UPS ON.
5
Press and hold the "ON/OFF/STANDBY" button
second. The alarm will beep once briefly after one second has
passed. Release the button.
Note: UPS system will function properly upon initial startup; however,
maximum runtime for the unit's battery will only be accessible after it
has been charged for 24 hours.
201203014 93-2757.indd 6
All manuals and user guides at all-guides.com
continued
unless you plan to hardwire the UPS system.)
4
B
.
C
will be visible after you remove
D
. Connect the
E
and the hardwire input panel
C
A
6
C
3A
E
INPUT
H
F
N
G
and the
3B
C
3C
.
F
.
G
.
D
4
A
for one
5
B
A
D
D
3/15/2012 5:03:43 PM