3
Install the battery connector cover under the EBM cable to provide strain relief.
Rotate the battery connector cover on its side and position under the EBM cable.
Connecting the EBM Cable
4
Plug the EBM cable into the UPS battery connector.
5
Secure the battery connector cover to the UPS rear panel using the screws removed in Step 2.
Configuring the UPS for an EBM
If the UPS is not configured for the EBM, the UPS reports less battery time remaining on the UPS front
panel and to any remote software. You may receive a shutdown warning prematurely. To ensure
maximum battery runtime when using power management software, configure the UPS for the EBM:
1
Press the
button for one second to go to the main menu selection and scroll down to the
Settings menu using the
2
Press the
button to enter the Settings menu.
3
Use the
button to scroll to the External Battery Module option and press the
The battery number value begins to flash.
|
6
Installation
All manuals and user guides at all-guides.com
button.
button.