5 – Remove Knockouts for All Main and Branch
Circuits
First drive the center knockout inward. The outer rings should then be
alternately pried up or driven in one at a time.
Drive the center knockout
inward, then the outer
rings.
6 – Pull Incoming Service and Branch Circuit
Wiring into Box
7 – Replace Interior
Drive in the mounting screws loosened in step 2.
8 – Wire Main, Neutral, and Equipment Ground
Refer to the rating label inside the equipment for the proper tightening
torques. Wire the neutral and equipment grounds only in the directions
indicated by the arrows in the figure below. For service entrance only,
the bond strap is provided.
Neutral
9 – Optional Wiring of Neutral and Ground
The neutral crossbar may be removed to provide optional neutral and
ground wiring as follows:
Main Breaker Service Entrance
with Bonding Screw
Uninsulated neutral or ground
See the rating label wiring diagram for an additional terminal kit.
Equipment
Ground
Neutral
Main Lug Only without
Bonding Screw
Insulated neutral or ground
Bond Screw
Insulated Ground
Or Neutral
Both sides
Crossbar
NOTE: If the load center is main breaker type and is not intended
for service entrance use, remove the bonding screw.
10 – Reinstall Service Entrance Barrier
Reinstall the service entrance barrier removed in step 2. Secure the
barrier with the two mounting screws.
11 – Wire Branch Circuits
Individually wire each branch circuit into a circuit breaker, then plug
the breaker into the interior. Refer to the label on the circuit breaker
for the proper tightening torque. Use only General Electric circuit
breakers specified on the load center rating label. Use of other circuit
breakers or components will void the load center warranty, may void
the UL listing, and can result in property loss or personal injury.
12 – Remove Cover Knockouts
13 – Important
Retighten all electrical connections before energizing the load center.
14 – Screw Front on Box
The adjustment for a flush mount is automatic when the cover is
installed.
15 – Identify Circuits
Use the labels provided to identify circuits for the user's convenience.
NOTE: Accessories and replacement parts are listed on the label
inside the load center.
Neutral
Terminal
A
Place screwdriver
here and tap with
hammer.