Télécharger Imprimer la page

Mitsubishi Electric MVZ-A12 AA4 Manuel D'installation page 25

Masquer les pouces Voir aussi pour MVZ-A12 AA4:

Publicité

Les langues disponibles

Les langues disponibles

14. Test run
14.1. Before test run
After completing installation and the wiring and piping of
the indoor and outdoor units, check for refrigerant leakage,
looseness in the power supply or control wiring, wrong polarity,
and no disconnection of one phase in the supply.
Use a 500-volt megohmmeter to check that the resistance
between the power supply terminals and ground is at least 1.0
MΩ.
Do not carry out this test on the control wiring (low voltage
circuit) terminals.
Warning:
Do not use the air conditioner if the insulation
resistance is less than 1.0 MΩ.
After installation or after the power source to the unit has been cut
for an extended period, the insulation resistance will drop below 1
MΩ due to refrigerant accumulating in the compressor. This is not a
malfunction. Perform the following procedures.
1. Remove the wires from the compressor and measure the
insulation resistance of the compressor.
2. If the insulation resistance is below 1 MΩ, the compressor is faulty
or the resistance dropped due the accumulation of refrigerant in the
compressor.
3. After connecting the wires to the compressor, the compressor will
start to warm up after power is supplied. After supplying power for
the times indicated below, measure the insulation resistance again.
14.2. Test run
Refer to the installation manual that comes with each remote controller for details.
14.3. Self-check
Refer to the installation manual that comes with each remote controller for details.
RF thermostat is not established.
[Output pattern A] Errors detected by indoor unit
IR wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp fl ashes
(Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
No sound
Wired remote controller
RF thermostat
Check code
P1
Intake sensor error
P2, P9
Pipe (Liquid or 2-phase pipe) sensor error
E6, E7
Indoor/outdoor unit communication error
P4
Drain sensor error
P5
Drain pump error
P6
Freezing/Overheating safeguard operation
EE
Communication error between indoor and outdoor units
P8
Pipe temperature error
E4
Remote controller signal receiving error
Fb
Indoor unit control system error (memory error, etc.)
– –
No corresponding
• The insulation resistance drops due to accumulation of refrigerant
in the compressor. The resistance will rise above 1 MΩ after the
compressor is warmed up for two to three hours.
(The time necessary to warm up the compressor varies according to
atmospheric conditions and refrigerant accumulation.)
• To operate the compressor with refrigerant accumulated in the
compressor, the compressor must be warmed up at least 12 hours to
prevent breakdown.
4. If the insulation resistance rises above 1 MΩ, the compressor is
not faulty.
Caution:

The compressor will not operate unless the power
supply phase connection is correct.

Turn on the power at least 12 hours before starting
operation.

Starting operation immediately after turning on the main
power switch can result in severe damage to internal parts.
Keep the power switch turned on during the operational
season.
Symptom
Remark
25

Publicité

loading

Ce manuel est également adapté pour:

M serieMvz- a18 aa4Mvz-a24 aa4Mvz-a30 aa4Mvz-a36 aa4