1. System description stratified layer module basic scheme (Scheme number 001 / 011)
The controller compares the temperature at collector sen-
sor S1 with the temperature at store sensor S2 (store 1).
If the temperature difference measured is higher than the
adjusted switch-on temperature difference, the pump (R1)
will be activated; the solar circuit will be heated.
The pump speed is controlled such that the adjustable tem-
perature difference is reached. If the temperature differ-
ence between S3 and S2 exceeds the adjusted switch-on
KIOTO Clear Energy AG
A - 9300 St. Veit a.d. Glan
DeltaSol
®
BX+ V2
S1
S2
RPD
1
2
3
4
S9
S10
V40
V40
VFD
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
Note: In scheme 011, connect the pump R1 to PWM A and R3 to PWM C additionally.
All manuals and user guides at all-guides.com
Vor Öffnen Gerät spannungslos schalten!
Isolate mains before removing cover!
Masse-Sammelklemme benutzen
Use ground common terminal block
Neutralleiter-Sammelklemme benutzen!
N
Use neutral conductor common terminal block
Schutzleiter-Sammelklemme benutzen
Use PE Common terminal block
Temp. Sensor
S3
S4
S5
S6
S7
S8
5
6
7
8 9 10 11 12 13 14 15 16
PWMA
PWMB
PWMC
PWMD
CS10 VBus
0-10V
0-10V
0-10V
0-10V
S1
S3
S5
R1
temperature difference for the secondary pump (external
heat exchanger), the secondary pump (R3) will be switched
on. Store loading is controlled by means of an additional
heat exchange function. The valve (R4) is normally open to
load the central store zone.
If the temperature difference between S5 and S7 exceeds
the switch-on temperature difference, the upper store
zone will be loaded up to the adjusted set temperature.
R1-R4
1 (1) A (100 ... 240) V~
R5
4 (1) A 240 V~
4 (1) A 24V
IP20
S7
R4
(V1)
Speicher
Store 1
1
S2
R3
T4A
100 ... 240 V~
50-60 Hz
L' L
N
11
|