7
Commissioning
Commissioning steps
Commissioning steps
)
Note!
Do not change the setting sequence.
Step−by−step commissioning of the function module with the DRIVECOM device control is
described below.
Step
Procedure
1.
Configure the host (master) for communication via the function
module.
2.
Inhibit the standard device via terminal 28 (CINH).
l
Set terminal 28 to LOW level.
l
Later on the standard device can be inhibited and enabled via the
bus system.
3.
Set DIP switch S1:
l
Setting for the last node = OFF
l
Setting for all other nodes = ON
4.
Define user data length via ...
l
DIP switches S2 ... S4 or
l
code C1515
5.
Connect the mains voltage and, if available, the separate voltage
supply for the function module.
l
The standard device is ready for operation after approx. 1 second.
l
Controller inhibit (CINH) is active.
Response
l
The green LED "Connection status to standard device" at the front
of the function module is lit (only visible in the case of the 8200
vector).
l
Keypad:
6.
It is now possible to communicate with the standard device, i.e. all
codes can be read and all writable codes can be adapted to the
application.
Response
The yellow LED on the function module is blinking when the
INTERBUS is active.
7.
If PCP communication is used, carry out the PCP service "initiate".
l
It is now possible to access the parameters of the standard device
with the PCP services "read" and "write".
52
dc
(if attached)
l
Detailed
information
^ 54
Documentation
for the standard
device
^ 57
^ 55
^ 58
^ 59
Documentation
for the standard
device
^ 59
INTERBUS
communication
manual