DTI cooling unit assembly (installation)
Item
Designation
1
Air inlet
3
Device contour
Attach cut-outs to the DTI cooling unit
Requirements
-
All general requirements have been fulfilled; see
-
The unit is de-energized.
Required tools and material
-
Saw
-
Use a switch cabinet cutter, if applicable
-
Protective covers
Procedure
▪ Use a protective cover to protect the switch cabinet from chips.
▪ Provide the switch cabinet with cut-outs. For the prescribed dimensions, refer to the figure switch cabinet
exterior view.
▪ The four corner cut-outs can be rectangular or have a maximum R = 4 mm.
▪ Deburr the cut edges.
▪ Remove chips and assembly waste from the switch cabinet.
Cut-outs have been attached.
Operating Manual DTS and DTI 6201C / 6301C Standard Controller (SC) 086100015c © Pfannenberg GmbH
1
3
Figure 12 - Switch cabinet exterior view
DTI cooling unit cut-outs
General assembly requirements
2
Item
Designation
2
Air outlet
Page 18 / 39