Controller
The controllers are regulating units for the adjustment of refrigeration functions and operating data. They enable
readouts of system messages and diagnostic data. The controllers have a service interface which enables various
configurations. There is also a connection for collective fault indications.
Cooling units with a standard controller (SC) have a display unit with a green LED light (1). The display unit is
located on the unit cover. Permanent illumination of the green LED light (1) while the mains voltage is connected
indicates fault-free operation. The LED light (1) begins if there is an operational fault or a malfunction. For detailed
information about the error messages, see
2.4.3
DIP switch
1
Figure 4 – Positioning of the controller
The DIP switch(2) on the control circuit board enables regulation and control(1) of setpoints and limit values for
temperatures; see
DIP switch.
 Position 4 on the DIP switch(2) controls the adjustment of the temperature unit.
Optional control °C to °F (OFF = °C / ON = °F).
 The DIP switch(2) is located on the controller(1), see
 The settings of the DIP switch(2) are adopted at the time of commissioning.
The following values are set in the condition as supplied from the factory:
The switch cabinet temperature setpoint is 35°C.
The maximum switch cabinet temperature is 50°C.
Operating Manual DTS and DTI 6201C / 6301C Standard Controller (SC) 086100015c © Pfannenberg GmbH
1
Figure 3 – Standard controller (SC) operating display
Error
messages
electrical circuit diagram
.
2
Abbildung 5 – Location DIP switch /Controller
and
3
1
DIP switch .
Page 8 / 39