Les langues disponibles

N°REG.
Register
2
SensorPI
EN
3
Sensor1
4
Sensor2
5
PIRange
6
SetPoint
7
Kp
8
Ki
9
Kq
10
PulsosEncoder
11
MinOut
12
MaxOut
13
S1Alarm
14
S2Alarm
15
MinRPM
16
VacMIN
17
IN1 Range
60
Min.
Max.
Description
0=Interno
1=IN1 0-10V
0
4
2=IN1 4-20mA
3=IN2 0-10V
4=IN2 4-20mA
1=0-10V %HR
2=4-20mA %HR
3=0-10V °C
0
7
4=4-20mA °C
5=0-10V CO2
6=4-20mA CO2
7=NTC 100K
1=0-10V %HR
2=4-20mA %HR
0
6
3=0-10V °C
4=4-20mA °C
5=0-10V CO2
6=4-20mA CO2
50
1250
SensorPI=0
50
2500
SensorPI<>0
100
9900
Sensor<>0
0=Interno
1=IN1 0-10V
2=IN1 4-20mA
0
5
3=IN2 0-10V
4=IN2 4-20mA
5=ConsolaMODBUS
(PROSYS ECOWATT)
1
250
Increases 1
1
250
Increases 1
50
300
Increases 1
0
16
Increases 1
0
50
Increases 5%
50
100
Increases 5%
0
100
Increases 5%
0
100
Increases 5%
100
500
Increases de 100
80
150
Increases de 10
0
100
%HR incrementos
0
50
°C incrementos
0
2000
PPM incrementos
Default
0
0=NO
0
0=NO
0
400Pa
600Pa
(CRVB-N 250)
5
20
20
100
(CTB/4-500/200)
84
(CTB/4-800/250)
94
(CTB/4-1300/315)
70
(CRVB-N 250)
88
(CRHB/CRVB-N 280)
112
(CRHB/CRVB-N 315)
147
(CRHB/CRVB-N 355)
2
(CTB/4-400/160)
(CTB/4-500/200)
5
(CTB/4-800/250)
(CTB/4-1300/315)
1
CRVB-N 250
CRHB/CRVB-N 280
CRHB/CRVB-N 315
CRHB/CRVB-N 355
0
100
90
90
400
80
100
Comments
Sensor type in PI
PRESSURE or PI VOLUME
mode
Sensor type in
PROPORTIONAL mode
and analog input signal 1
Sensor type in
PROPORTIONAL mode
and analog input signal 2
Range sensor in PI
PRESSURE mode
Set point in PI PRESSURE
mode
Proportional constant in PI
PRESSURE mode
Integral constant in PI
PRESSURE mode
Airflow constant with
pressure sensor
Number of pulses for
encoder lap
Minimum output value
Maximum output value
Analog input 1 alarm
Analog input 2 alarm
Min RPM alarm
Minimum voltage AC
motor
Background scale in
proportional mode input 1