10
Maintenance, Overhaul, Repair
10.1 Maintenance
• Consult the relevant local and national regulations to determine the type and extent of
inspections.
• Adapt inspection intervals to the operating conditions.
At a minimum, check the following points during maintenance work on the device:
• Firm fit of the conductors,
• Damage on the enclosure, seals or surface,
• Dirt on the sleeves,
• Compliance with the permissible temperatures (according to UL 60079),
• Whether the device is used in accordance with its intended use.
10.2 Overhaul
Overheating and explosion hazard due to defective switching contacts!
Non-compliance results in severe or fatal injuries.
• Replace the entire socket flange after each short circuit in the
Observe the relevant national regulations in the country of use.
10.3 Repair
Explosion hazard due to improper repair!
Non-compliance results in severe or fatal injuries.
• Repair work on the devices must be performed only by
Explosion hazard due to improper repair!
Non-compliance results in severe or fatal injuries.
• Hermetically sealed connections are to be repaired only in
• Repairs are not permitted.
287620 / 8570674300
2022‐03‐28·IO00·III·en·00
main circuit of the switch because the state of the switching
contacts cannot be checked in hermetically sealed equipment.
R. STAHL Schaltgeräte GmbH.
conformity with the manufacturer's description.
Maintenance, Overhaul, Repair
DANGER
DANGER
DANGER