Specifications
Response
Characteristic
Measuring rate
Response time t 99*
*) Time after change of input value until reaching an output value of 99% steady
state
Power supply
Broad-range power supply
Isolation
Test voltage
Working voltage
(basic insulation)
60
Rising / falling linearly; via IrDA:
curve defined by sampling points or
polynomials
Approx. 3 / s
Approx. 2 / s in operating mode:
thermocouple with ext. reference
junction compensation or
resistance measurement
5 k ... 100 kohms
300 ms
500 ms in operating mode:
thermocouple with ext. reference
junction compensation or
resistance measurement
5 k ... 100 kohms
24 V ... 110 V DC (± 20%), appr. 1.3 W
110 V ... 230 V AC (± 10%), 48 ... 62 Hz,
approx. 2.2 VA
2.5 kV, 50 Hz: Power supply against
input against output
Up to 300 V AC/DC across all circuits
with overvoltage category II and
pollution degree 2. For applications with
high working voltages, ensure there
is sufficient spacing or isolation from
neighboring devices and protection
against electric shocks.