G
®
THERMASGARD
Networkable outdoor temperature measuring transducer THERMASGARD
Bluetooth-enabled, in an impact-resistant plastic housing with quick-locking screws, optionally with ⁄ without display and bar graph. The on-wall
sensor is used to detect the temperature in gaseous media. It is used outdoors or in wet rooms, in cold storage buildings and greenhouses, in the
industrial sector and in agriculture. Installation on outside walls is preferably performed on the north side or in a protected place. In case of direct
solar irradiation, the weather and sun protection hood WS 03 (accessory) is to be used. The sensor is factory-calibrated.
EtherCATP-enabled measuring transducer for industrial requirements with maximum reliability: includes easy PLC integration using the device's ESI
configuration file, diagnostics (such as communication failure counter), advanced settings options, access to historical data (min / max) and
establishing the sensor's service interval. Optionally with large illuminated display (3-line, customised programming in the 7-segment and dot-matrix
range) and bar graph (7-digit, LEDs freely configurable) for graphical display, e.g., as a traffic light indicator.
TECHNICAL DATA
Power supply:
Power consumption:
Bus protocol:
Radio technology:
Sensor:
Measuring range:
Deviation in temperature:
Medium:
Protective tube:
Housing:
Dimensions:
Cable connection:
Ambient temperature:
Permitted humidity:
Protection class:
Protection type:
Standards:
Equipment:
ACCESSORIES
®
THERMASGARD
ATM 2 - EtherCAT P
Type ⁄ WG02
ATM 2-ECATP xx
AT M 2 - E C AT P
AT M 2 - E C AT P LCD
ACCESSORIES
WS-03
Weather and sun protection hood, 200 x 180 x 150 mm,
stainless steel V2A (1.4301)
ATM2 - EtherCAT P
24VDC via EtherCATP (U
)
S
< 3W
EtherCAT
Bluetooth (LE)
Pt1000, DIN EN 60751, class B (Perfect Sensor Protection)
–50...+150°C
typically ± 0.2K at +25°C
Clean air and non-aggressive, non-combustible gases
Stainless steel, V4A (1.4571), Ø = 6mm
(see dimensional drawing)
Plastic, UV-resistant, polyamide material, 30% glass-globe reinforced,
with quick-locking screws (slotted ⁄ Phillips head combination),
colour traffic white (similar to RAL 9016), housing cover for display is transparent!
126 x 90 x 50mm (Tyr 2)
M8 plug-in connector, EtherCATP-encoded
Measuring transducer –30...+70°C
< 95% r. H., non-precipitating air
III (according to EN 60 730)
IP 54 (according to EN 60 529) when built-in
CE conformity, according to EMC Directive 2014 ⁄ 30 ⁄ EU, according to RED 2014 ⁄ 53 ⁄ EU
Display with illumination, 3-line, customised programming, cutout approx. W 51 x H 29mm,
to display the actual temperature or a customised display value.
Bar graph, 7-digit, LEDs freely configurable, to graphically display the reading.
see last page
On-wall temperature sensor,
with EtherCATP port
Measuring Range
Sensor
Temperature
–50...+150 °C
Pt1000
–50...+150 °C
Pt1000
®
ATM2 - EtherCAT P with M8 plug-in connector (EtherCATP-encoded),
Output
Bar graph
Display
EtherCAT P
EtherCAT P
6
Rev. 2021-V11
Item No.
2001- 6201- 9100- 001
□ ■
2001- 6202- 9100- 001
7100- 0040-6000- 000