3.1 Normal Grounding Resistance Test 
 
a. 
Setting up the connection 
 
Refer to the Figure, align the auxiliary earth bar P1, the auxiliary earth bar C1 and the earth electrode 
E in a line. C1 and P1 must be 5 to 10 meters apart, P1 and E must be 5 to 10 meters apart. 
 
Drive the auxiliary earth bare C1 and P1 into the ground. Connect C1 to "C" terminal using the red 
normal‐test lead, connect P1 to "P" terminal using the yellow normal‐test Iead, connect the earth electrode E 
to be measured to "E" terminal using the gram normal‐test lead. 
 
 
              The grounds where P1 and C1 are driven must have high water content. For the dry ground, send 
ground and gravel ground, you must add water to the auxiliary earth  bare' positions. For cement ground, place 
the auxiliary earth bars an the ground, add  water to the bars' positions, then respectively cover the bare with 
damp towels, then do the measurement. 
 
 
b. Checking the connections 
 
b1. 
Checking the connection between "C" and "E" terminals: Set the  
 
function/range switch to a resistance range, then press "TEST" button. lf the LED gives green light, the 
connection between "C" and "E" terminals is good and the grounding resistance of the bar C1 is in permitted 
range. 
 
 
lf the LED gives red light, do the following steps until the LED doesn't give red light when you 
measure grounding resistance: 
 
 
Check the connection of the red normal‐fest lead. Check the connection of the  
 
green normal‐fest lead. Change the bar C1 to another permitted position. 
 
 
Add water to the bar C! position to reduce the bar's grounding resistance to a  
 
appropriate value. 
 
b2. 
Checking the connection of the yellow normal‐test lead: Remove the red  
 
normal‐fest lead from "C" terminal, move the plug of the yellow normal‐test lead to "C" terminal ( the 
yellow clip is still connected to bar P1). Set the function/range switch to a resistance range, then press 'TEST" 
button. If the LED gives green light, the connections are good, and the grounding resistance of the bar P1 is in 
permitted range. 
 
 
If the LED gives red Iight, check the connections or change the bar P1 to  
 
another permitted position or add water in the position of bar P7 to reduce its  
 
grounding resistance. 
 
b3. 
Checking with a known resistor 
 
 
Use a resistor of 100 to check. Connect the red clip and the yellow clip to one  
 
terminal of the resistor, connect the green clip to the resistor's another  
 
terminal. Set the Function/Range switch to "200 Ohm" Position, press "TEST" button. If the reading on 
the display is about "100.0 Ohm", the three normal‐ fest Ieads are good, otherwise the fester or at least one 
normal‐test lead  connection is bad. Note: The red normal‐fest lead is connected to "C" 
 
 
terminal, the yellow normal‐test Iead is connected to "P" terminal, the green  
 
normal‐fest Iead is connected to "E" terminal. 
 
 