Télécharger Imprimer la page

Testboy TV 440N Mode D'emploi page 14

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 20
  
INSTRUCTIONS 
1.           Display 
2.           "TEST" button 
 
This button can be used to Start or stop grounding resistance fest alter you switch the   fester an and 
set the FuncbonlRange to a resistance Tange. After you press this   button, hie grounding resistance fest 
begins. Ahout 30 seconds later, the test  automatically stups. If you want to stop the fest ahead of time, just 
press this button again. 
 
 
3.          "LOCK" key (for continuous grounding resistance test) 
 
After you press this key when the grounding resistance fast is on, "LOCK" appears on   the display, 
and the grounding resistance test will last until you press TEST buttan again. 
4. 
"HOLD" key 
 
To hold the present reading, just press this key and " appears as an indication. To exit   Data Hold 
mode, press this key again. 
5. 
"*"key 
 
Press this key to enable the backlight function. About 15 seconds later, the backlight will go off 
automatically 
6. 
Function / Range switch 
 
This switch can be used to tum onloff the tester as well as to select desired Tange or function. 
7. 
LED 
 
After you press the "TEST" Button with the function/range switch in a resistance range, the LED lights 
to indicate that the grounding resistance test circuit is working. If the LED gives green light, it means that the 
tester is working normally. If the LED gives red light, it means the resistance between "C" terminal and "E" 
terminal is out of the permitted range. 
 8. 
 "C" terminal 
 
lt is a current terminal for grounding resistance test. lt is to be connected to the auxiliary earth bar 
which is farther away from the earth electrode to be tested in normal grounding resistance fest (refer to Figure 
2 ). 
9. 
"P" terminal 
 
lt is a voltage terminal for grounding resistance fest, lt is to be connected to the auxiliary earth bar 
which is nearer to the earth electrode to be tested in normal grounding resistance fest. (refer to Figure 2 ) 
10. 
"E" terminal 
 
In grounding voltage test, it is a common terminal. 
 
In grounding resistance fest, it is to be connected ta the earth electrode to be tested,  