Tabella parametri supervisione SW mul chiller 1.6 / Parameters table oversight mul chiller SW 1.6
MULTICHILLER (ANALOG VARIABLE 129 = 0 = default value)
BMS address
Descrip on
1
In (Common Inlet water temperature read by mul chiller
)
2
Out (Common Outlet water temperature read by
mul chiller)
3
Global Chiller Cooling Setpoint
4
Global Chiller Hea ng Setpoint
5
Global Actual Cooling Setpoint
6
Global Actual Hea ng Setpoint
7
Global Chiller 2° Cooling Setpoint
8
Global Chiller 2° Hea ng Setpoint
9
Delta temperature chiller full load
10
Delta setpoint in setpoint reset Off
11
Delta setpoint in setpoint reset On
12
Leaving water temp. start chiller (on cooling)
13
Return water temp. shigh chiller 2 (on cooling)
14
Return water temp. shigh chiller 3 (on cooling)
15
Return water temp. shigh chiller 4 (on cooling)
16
Return water temp. shigh chiller 5 (on cooling)
17
Return water temp. shigh chiller 6 (on cooling)
18
Return water temp. shigh chiller 7 (on cooling)
19
Return water temp. shigh chiller 8 (on cooling)
20
Return water temp. shigh chiller 9 (on cooling)
21
Leaving water temp. start chiller (on hea ng)
22
Return water temp. shigh chiller 2 (on hea ng)
23
Return water temp. shigh chiller 3 (on hea ng)
24
Return water temp. shigh chiller 4 (on hea ng)
25
Return water temp. shigh chiller 5 (on hea ng)
26
Return water temp. shigh chiller 6 (on hea ng)
27
Return water temp. shigh chiller 7 (on hea ng)
28
Return water temp. shigh chiller 8 (on hea ng)
29
Return water temp. shigh chiller 9 (on hea ng)
30
Setpoint compensa on 1 On (On cooling)
31
Setpoint compensa on 2 On (On cooling)
32
Setpoint compensa on 3 On (On cooling)
33
Setpoint compensa on 4 On (On cooling)
34
Setpoint compensa on 5 On (On cooling)
35
Setpoint compensa on 6 On (On cooling)
36
Setpoint compensa on 7 On (On cooling)
37
Setpoint compensa on 8 On (On cooling)
38
Setpoint compensa on 1 On (On hea ng)
39
Setpoint compensa on 2 On (On hea ng)
40
Setpoint compensa on 3 On (On hea ng)
41
Setpoint compensa on 4 On (On hea ng)
42
Setpoint compensa on 5 On (On hea ng)
43
Setpoint compensa on 6 On (On hea ng)
44
Setpoint compensa on 7 On (On hea ng)
45
Setpoint compensa on 8 On (On hea ng)
46
TUA2 Outlet water temperature sensor SUW2 read by
mul chiller
47
TUA3 Outlet water temperature sensor SUW3 read by
mul chiller
48
Actual Load % (based on Load regula on)
42
UOM
Min
Max
A=Analogic D= Digital
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
Read / Write
R
R
R/W
R/W
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R