WV4460E Power Vent Water
Heater Controls
APPLICATION
The WV4460E Water Heater Control System is designed
for power vent water heater applications.
The WV4460E provides these features:
• Gas regulation and manual valve features
• Intermittent spark-to-pilot ignition
• Flame supervision using flame rectification sensing
through the spark rod. This flame sense circuit uses
patented technology to create a robust sensing
signal that is independent of AC line polarity and
appliance earth grounding.
• Water temperature sensing using solid state sensors
potted in a submersion well assembly
• Manually resettable High Temperature Cutout (TCO)
• Induced draft blower motor control
• Draft proving switch sensing via pressure switch
• Variable resistance flammable vapor sensor with a
sensing and control algorithm to provide automatic
shutdown when hydrocarbon vapors such as gasoline
are detected
• Retains up to 10 fault code histories in non-volatile
memory (available through the EnviraCOM™
communication port)
• Solid state setpoint adjustment over a factory preset
temperature range using a linear potentiometer to
provide high resolution adjustment
Special control features are available to address items
such as stacking. See a Resideo Product Specialist for
more information.
The specific application of the WV4460E System is the
responsibility of the appliance manufacturer. See the
Specifications below for temperature ranges and
regulator types. The WV4460E system refers to the
combination of the valve (VT8804A) and the electronic
control module (WT4834Q).
INSTALLATION INSTRUCTIONS
SPECIFICATIONS
IMPORTANT
WV4460E Controls provide direct replacement
only; do not substitute other models.
Body Pattern: 90 degree with 1/2 in. inlet and 1/2 in.
inverted flare outlet.
Natural gas model has right-hand threaded inverted
outlet.
LP gas model has left-hand threaded inverted outlet.
Mounting: Mounting in upright position only.
Electrical Tolerences:
Voltage Minimum: 98 Vac, 60 Hz.
Voltage Maximum: 132 Vac, 60 Hz.
Current in Running Mode: 0.1 Amps @ 120 VAC (plus
inducer motor draw)
Current in Idle Mode: 0.1 Amps @ 120 VAC
Inducer Motor drive rating: 3.5 Amps FLA and 7.0 Amps
LRA for 30,000 cycles
Capacity: See Table 1.
Conversion: Use conversion factors in Table 2 to convert
capacities for other gases.
Regulation Range (Btuh);
With 1/2 in. NPT inlet and 1/2 in. Inverted Flare Outlet:
Natural Gas:
Minimum: 30,000
Maximum: 100,000
LP Gas:
Minimum: 40,000.
Maximum: 100,000
Temperature Range:
Operating 0°F to 150°F (-18°C to 66°C)*
Storage -40°F to 175°F (-40°C to 79°C)
* Gas valve regulation range is guaranteed from 32°F to
150°F (0°C to 66°C)
Humidity:
90% Non-condensing at 95°F
69-1872EF-03

Publicité

Table des Matières
loading

Sommaire des Matières pour resideo WV4460E

  • Page 1 Temperature Range: Operating 0°F to 150°F (-18°C to 66°C)* The specific application of the WV4460E System is the Storage -40°F to 175°F (-40°C to 79°C) responsibility of the appliance manufacturer. See the * Gas valve regulation range is guaranteed from 32°F to Specifications below for temperature ranges and 150°F (0°C to 66°C)
  • Page 2 , 0.64 specific gravity natural gas at 0.25 kPa pressure drop). Valves are guaranteed at only 77 percent of the rating. Fig. 1. Typical capacity curve for WV4460E Family Water Heater Control System. Table 2. Gas Capacity Conversion Factor. Specific Gravity...
  • Page 3: Planning The Installation

    Proper insulation or shielding should be provided by the appliance manufacturer. Verify proper 125 mm air circulation is maintained when the appliance is installed. 100 mm M24184A Fig. 2. WV4460E dimensions in inches (mm). 69-1872EF—03...
  • Page 4 WELL ASSEMBLY connections to prevent electrical shock or M24214B equipment damage. Fig. 3. Mounting the WV4460E on the water heater tank. Location The WV4460E is mounted on the outside of the water heater tank. See Fig. 3. Install Control to Water Tank 1.
  • Page 5: Connect Gas Supply

    WV4460E POWER VENT WATER HEATER CONTROLS Connect Gas Supply DROP PIPED HORIZONTAL WARNING SUPPLY Fire or Explosion Hazard. Can cause severe injury, death, or property damage. Check for gas leaks with soap and water solution any time work is done on a gas system.
  • Page 6 WV4460E POWER VENT WATER HEATER CONTROLS 4. Connect the 5-wire electrical harness to the Con- ON/OFF SWITCH trol. BLUE LED 5. Connect the 2-wire flammable vapor sensor (TOD APPLY WRENCH FVS) to the Control. HERE WHEN CONNECTING 6. Connect the Pilot Assembly lead to the Spark con- SUPPLY LINE nector.
  • Page 7 WV4460E POWER VENT WATER HEATER CONTROLS Perform Gas Leak Test Perform Gas Input and Burner Ignition Check and Adjustment WARNING WARNING Fire or Explosion Hazard Can cause severe injury, death, or property Fire or Explosion Hazard damage. Can cause severe injury, death, or property Check for gas leaks with soap and water solution damage.
  • Page 8: Sequence Of Operations

    WV4460E POWER VENT WATER HEATER CONTROLS c. Make sure electrical connections are clean and 3. Consequence of unexpected shutdown. Where the tight. cost of an unexpected shutdown would be high, the d. Check for cracked ceramic Insulator, which can system should be checked more often.
  • Page 9 WV4460E POWER VENT WATER HEATER CONTROLS Sequence Mode Description Temperature reaches setpoint The demand for heat is satisfied (temperature reaches set point). De-energize the main and pilot gas valves The gas valves are de-energized. Monitor Flame Flame is monitored until flame signal drops below Flame Lost level.
  • Page 10 WV4460E POWER VENT WATER HEATER CONTROLS Green LED Status Indicates Check/Repair Six-Two Flash, Soft Lockout - Recycle Limit - PS/Limit • Check venting to insure pressure switch is not three second opened momentarily opening as the appliance warms. pause • Check vent outlet for wind-gust problems.
  • Page 11 WV4460E POWER VENT WATER HEATER CONTROLS CHECK: SLIDE SWITCH TO THE ON POSITION, TANK TEMPERATURE IS AT OR CLOSE TO HOT SET POINT TURN THE SET KNOB TO HOT; WIRING OF LINE VOLTAGE SUPPLY INDUCER SHOULD START INDUCER WIRING, INCLUDING L2 RETURN...
  • Page 12: Turning Off The Appliance

    Resideo Technologies, Inc. 1985 Douglas Drive North, Golden Valley, MN 55422 1-800-468-1502 69-1872EF—03 M.S. Rev. 05-20 | Printed in United States www.resideo.com © 2020 Resideo Technologies, Inc. All rights reserved. This product is manufactured by Resideo Technologies, Inc. and its affiliates.
  • Page 13: Régulateurs De Chauffe-Eau Power Vent Wv4460E

    32 °F à 150 °F (0 °C à 66 °C) de température et les types de régulateurs. Le système WV4460E est constitué de la vanne (VT8804A) et du Humidité : 90 % Sans condensation à 95 °F module de régulation électronique (WT4834Q).
  • Page 14: Pièces Accessoires (Commande Séparée)

    — Ensembles de puits : Réf. 50013231-001 : 3/4 po NPT, 1 po isolation, 3 po — Consulter un spécialiste des produits Resideo pour les insertion. Capteur limiteur pour une utilisation avec autres accessoires disponibles. les vannes à gaz de chauffe-eau WV4460E.
  • Page 15: Préparation De L'installation

    RÉGULATEURS DE CHAUFFE-EAU POWER VENT WV4460E PRÉPARATION DE Nettoyage à l’eau ou à la vapeur Si le régulateur se mouille, le remplacer. Si l’appareil est L’INSTALLATION susceptible d’être lavé à l’eau ou à la vapeur, protéger (couvrir) le régulateur et le câblage de l’eau ou de la vapeur.
  • Page 16: Emplacement

    LE PUITS Risque de choc électrique. MF24214A Peut causer des dégâts et des blessures graves, Fig. 3. Montage du WV4460E sur le réservoir du chauffe- voire mortelles. eau. Débrancher l’alimentation avant d’effectuer les connexions de câblage pour éviter les chocs électriques et les dégâts de l’équipement.
  • Page 17: Brancher L'alimentation En Gaz

    RÉGULATEURS DE CHAUFFE-EAU POWER VENT WV4460E Brancher l’alimentation en gaz COLONNE DESCENDANTE ALIMENTATION AVERTISSEMENT HORIZONTAL EN GAZ (TUYAU) Risque d’incendie ou d’explosion. Peut causer des dégâts et des blessures graves, voire mortelles. Vérifier l’absence de fuites de gaz avec une solution savonneuse à...
  • Page 18: Remplissage Du Réservoir

    RÉGULATEURS DE CHAUFFE-EAU POWER VENT WV4460E 5. Brancher le capteur de vapeurs inflammables à INTERRUPTEUR deux fils (FVS TOD) sur le régulateur. MARCHE/ARRÊT DEL VERTE 6. Brancher le fil de la veilleuse au connecteur METTRE LA CLÉ ICI POUR d’étincelle...
  • Page 19: Test De Fuite De Gaz

    RÉGULATEURS DE CHAUFFE-EAU POWER VENT WV4460E régler pour qu’elle soit confortable au toucher. comme décrit dans le formulaire 70-2602, manuel Considérer l’âge et la santé de tous ceux qui des régulateurs à gaz, et comparer la valeur d’entrée entreront en contact avec l’eau chaude.
  • Page 20: Entretien

    RÉGULATEURS DE CHAUFFE-EAU POWER VENT WV4460E 4. Environnement poussiéreux, mouillés ou corrosifs. ENTRETIEN Ces environnements pouvant causer une détérioration plus rapide du régulateur, le système doit être vérifié plus souvent. AVERTISSEMENT Le système doit être remplacé dans les cas suivants : Risque d’incendie ou d’explosion.
  • Page 21: Dépannage

    RÉGULATEURS DE CHAUFFE-EAU POWER VENT WV4460E Séquence Mode Description La température atteint le point de L’appel de chauffage est satisfait (la température atteint consigne le point de consigne). Désactivation des vannes de gaz Les vannes de gaz sont désactivées. principale et de veilleuse Surveillance de flamme La flamme est contrôlée jusqu’à...
  • Page 22 RÉGULATEURS DE CHAUFFE-EAU POWER VENT WV4460E Statut de la DEL verte Indique Vérification/réparation Six séquences de deux Verrouillage de premier • Vérifier la ventilation pour s’assurer que le pressostat ne s’ouvre pas momentanément pendant que l’appareil chauffe. clignotements, pause niveau – Source •...
  • Page 23 RÉGULATEURS DE CHAUFFE-EAU POWER VENT WV4460E VÉRIFIER : METTRE L’INTERRUPTEUR SUR MARCHE, TOURNER LE BOUTON DE LA TEMPÉRATURE DU RÉSERVOIR DOIT ÊTRE ÉGALE RÉGLAGE SUR CHAUD; L’INDUCTEUR AU/PROCHE DU POINT DE RÉGLAGE DOIT DÉMARRER CÂBLAGE DE L’ALIMENTATION TENSION SECTEUR CÂBLAGE DE L’INDUCTEUR, RETOUR L2 INCLUS CAPTEUR DE TEMPÉRATURE ET CAPTEUR DE VAPEURS...
  • Page 24: Instructions Au Propriétaire

    Resideo Technologies, Inc. 1985 Douglas Drive North, Golden Valley, MN 55422 1-800-468-1502 69-1872EF—03 M.S. Rev. 05-20 | Imprimé aux États-Unis www.resideo.com © 2020 Resideo Technologies, Inc. Tous droits réservés. Ce produit est fabriqué par Resideo Technologies, Inc. et ses sociétés affiliées.

Table des Matières