Connect Gas Supply

WARNING
Fire or Explosion Hazard.
Can cause severe injury, death, or property
damage.
Check for gas leaks with soap and water solution
any time work is done on a gas system.
Follow these warnings exactly:
1. IF YOU SMELL GAS:
a. Turn off the gas supply at the appliance service
valve. On LP gas systems, turn off the gas sup-
ply at the gas tank.
b. Do not light any appliances.
c. Do not touch electrical switches or use the
phone in the building.
d. Leave the building and use a phone to call the
gas supplier.
e. If you cannot reach the gas supplier, call the fire
department.
2. The water heater control must be replaced in event
of any physical damage, tampering, bent terminals,
missing or broken parts, stripped threads, or evi-
dence of exposure to heat.
CAUTION
Contamination Hazard.
Can cause the device to malfunction.
Do not use thread tape sealants to seal the gas
supply to the control.
a. Use a pipe dope compound to seal the inlet
pipe thread connection. On LP installations,
use a compound resistant to LP gas.
b. Use only ANSI approved compounds.
All piping must comply with local codes and ordinances
or with the National Fuel Gas Code (ANSI Z223.1 NFPA
No. 54), whichever applies. Tubing installation must
comply with approved standards and practices.
1. Ensure that the gas supply is turned off.
2. Use new, properly reamed pipe free from chips. If
tubing is used, make sure the ends are square,
deburred and clean. All tubing bends must be
smooth and without deformation.
3. Run pipe or tubing to the water heater control. If
tubing is used, obtain a tube-to-pipe coupling to
connect the tubing to the control.
4. Install a sediment trap in the supply line to the
water heater control. See Fig. 5.
Table 3. NPT Pipe Thread Length (in.).
Pipe
Thread Pipe This
Size
Amount
1/2
3/4
Maximum Depth Pipe can
be inserted into Control
1/2
WV4460E POWER VENT WATER HEATER CONTROLS
DROP
PIPED
HORIZONTAL
GAS
SUPPLY
3 IN.
(76 MM)
MINIMUM
DROP
HORIZONTAL
TUBING
GAS
SUPPLY
1
RISER
3 IN.
(76 MM)
MINIMUM
WARNING
EXPLOSION HAZARD.
FAILURE TO FOLLOW PRECAUTIONS CAN
RESULT IN A GAS-FILLED WORK AREA.
SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING END CAP.
TEST FOR GAS LEAKAGE WHEN INSTALLATION IS COMPLETE.
1
ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH.
Fig. 5. Install a sediment trap in the supply line.
5. Apply a moderate amount of good quality pipe
compound, leaving two end threads bare. On LP
installations, use a compound resistant to LP gas.
See Fig. 6.
APPLY A MODERATE AMOUNT OF
PIPE COMPOUND ONLY TO PIPE
(LEAVE TWO END THREADS BARE).
Fig. 6. Use moderate amount of pipe compound.
6. Remove the seals over the water heater control
inlet and outlet, if necessary.
7. Connect the pipe to the water heater control inlet to
a maximum of 45 ft-lb of torque. Use a wrench on
the square end of the water heater control. Refer to
Fig. 7.
f.
Natural gas model is right-hand threaded
g. LP gas model is left-hand threaded
5
WV4460E
WV4460E
M13681A
TWO
IGNITION
IMPERFECT
SYSTEM
THREADS
CONTROL
PIPE
THREAD PIPE THE AMOUNT
SHOWN IN TABLE 3 FOR INSERTION
INTO IGNITION SYSTEM CONTROL
69-1872EF—03
M24210A