Features
• One or two switch models available
• Independent switch adjustment on two switch models, no tools
needed
• Two 1/2" conduit/cable entrances
• Separate isolated wiring chambers
• Non-corrosive pressure connection
• Non-Conductive Enclosure
• VdS version available
• Available with Nylon or Brass pressure connection (Nylon
connection shown in picture).
This document contains important information on the installation
and operation of PS40 pressure switches. Please read all instructions
carefully before beginning installation. A copy of this document is
required by NFPA 72 to be maintained on site.
Installation
The Potter PS40 Series Supervisory Pressure Actuated Switches are
designed primarily to detect an increase and/or decrease from normal
system pressure in automatic fire sprinkler systems. Typical applications
are: air/nitrogen supervision in dry pipe and pre-action systems, pressure
tanks, air supplies, and water supplies. The PS40-1 has one switch and
is factory set to activate at approximately 30 psi (2,1 bar) on a decrease
in pressure. The PS40-2 has two switches. The Low switch is factory set
to activate at approximately 30 psi (2,1 bar) on a decrease in pressure.
The High switch is factory set to activate at approximately 50 psi (3,5
bar) on an increase in pressure. NFPA 72 requires a supervisory signal
if the pressure increases or decreases by 10 psi from normal. The PS40
is factory set for a normal air pressure of 40 psi. See section heading
Adjustments and Testing if other than factory set point is required.
1.
Connect the PS40 to the system side of any shutoff or check valve.
2.
Apply Teflon tape to the threaded male connection on the device.
(Do not use pipe dope)
3.
Device should be mounted in the upright position. (Threaded
connection down)
4.
Tighten the device using a wrench on the flats on the device.
Potter Electric Signal Company, LLC
St. Louis, MO
Phone: 866-956-0988 / Canada 888-882-1833
5400931 - REV J
Supervisory Pressure Switch
Technical Specifications
Two knockouts for 1/2" conduit provided. Individual switch
Conduit Entrances
compartments and ground screw suitable for dissimilar voltages
SPDT (Form C)
Contact Ratings
10.1 Amps at 125/250 VAC, 2.0 Amps at 30 VDC
One SPDT in PS40-1, Two SPDT in PS40-2
Cover incorporates tamper resistant fastener that requires a special
Cover Tamper
key for removal. One key is supplied with each device.
Typical 1 lb. at 10 psi (,07 at ,7 bar)
Differential
4 lbs at 60 psi (,28 at 4,1 bar)
Dimensions
3.78"(9,6cm)Wx3.20"(8,1cm)Dx4.22"(10,7cm)H
Cover: Weather/UV/Flame Resistant High Impact Composite
Enclosure
Base: Die Cast
All parts have corrosion resistant finishes
-40º F to 140ºF (-40ºC to 60ºC)
Environmental
NEMA 4/IP66 Rated Enclosure indoor or outdoor when used with
Limitations
NEMA 4 conduit fittings
PS40-1 operates on decrease at 30 psi (2,1 bar)
Factory Adjustment
PS40-2 operates on increase at 50 psi (3,5 bar) and on decrease at
30 psi (2,1 bar)
Maximum System
300 psi (20,68 bar)
Pressure
Pressure Connection
1/2" NPT male Nylon or optional Brass
Pressure Range
10-60 psi (,7-4,1 bar)
Service Use
NFPA 13, 13D, 13R, 72
*Specifications subject to change without notice.
2/20
PS40 Series
www.pottersignal.com
PAGE 1 OF 8

Publicité

Table des Matières
loading

Sommaire des Matières pour Potter PS40 Serie

  • Page 1 NFPA 72 to be maintained on site. Installation Technical Specifications The Potter PS40 Series Supervisory Pressure Actuated Switches are Two knockouts for 1/2” conduit provided. Individual switch Conduit Entrances designed primarily to detect an increase and/or decrease from normal compartments and ground screw suitable for dissimilar voltages system pressure in automatic fire sprinkler systems.
  • Page 2: Wiring Instructions

    The use of a Potter BVL (see product bulletin 5400799 for details) under the terminal. is recommended to facilitate setting and testing of the PS40 pressure switch.
  • Page 3 High Pressure Signal Connection Fig 6 TO FIRE ALARM PANEL Removing Knockouts EOLR Fig 9 DWG# 928-2 DWG#928-5 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-0988 / Canada 888-882-1833 • www.pottersignal.com • 5400931 - REV J...
  • Page 4: Ordering Information

    A Model BVL bleeder valve as supplied by Potter Electric Signal Company of St. Louis, MO., or equivalent shall be connected...
  • Page 5: Caractéristiques

    Les commutateurs de surveillance actionnés par pression de la série Le dispositif est muni de deux entrées défonçables pour des conduits PS40 de Potter ont été conçus principalement pour détecter une Entrée des conduits de 1/2". Des compartiments individuels pour chaque commutateur et des vis de terre adaptées en cas de tensions différentes ont été...
  • Page 6: Plaque À Bornes Pour Le Raccordement Du Commutateur

    L’utilisation d’un robinet de purge BVL Potter (voir la fiche produit 5400799) est recommandée afin de faciliter les procédures de réglage et d’essai du commutateur de pression PS40.
  • Page 7: Raccordements Électriques Types

    VERS CENTRALE TO FIRE ALARM PANEL D'ALARME INCENDIE Ouvrir les entrées défonçables. EOLR Fig 9 DWG# 928-2 DWG#928-5 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-0988 / Canada 888-882-1833 • www.pottersignal.com • 5400931 - REV J...
  • Page 8: Spécifications Ingénieur / Architecte Commutateur De Débit À Pression

    Commutateur de surveillance de pression : il doit s’agir d’un modèle • Risque d’électrocution. Débrancher l’alimentation électrique avant PS40 tel que fabriqué par Potter Electric Signal Company, St Louis toute intervention. Cela pourrait provoquer de graves blessures MO et doit être installé sur le système de gicleurs conformément aux voire la mort.

Table des Matières