Features
• assembled in USa
• Fits most lever/tee type ball valves up to 2"
• Fits most backflow preventers up to 2"
• Operates on open or closed valves
• Includes mounting hardware to supervise coils on most
solenoids
• accommodates up to 12 aWg wire
• Optional field installed cover tamper switch kit (0090224)
• RoHS compliant
NOTICE
Before any work is done on the fire sprinkler or fire alarm system, the
building owner or their authorized representative shall be notified.
Before opening any closed valve, ensure that opening the valve
will not cause any damage from water flow due to open or missing
sprinklers, piping, etc.
Important: This document contains important information on the installation and operation of the RBVS Universal Ball Valve/Solenoid Coil Supervisory
Switches. please read all instructions carefully before beginning installation. a copy of this document is required by NFpa 72 to be maintained on site.
Description
The Model RBVS is designed to monitor the fully open or closed
position of a ball valve installed in a sprinkler system as well as monitor
the position of a coil on a solenoid for a preaction/deluge system. The
unit will fit on most ball valves installed on back-flow-preventers and
alarm trim lines of dry, alarm, and deluge sprinkler valves. The switch
operates if the ball valve handle is moved from the normal position.
However, the switch does not track the position of the handle or ball.
When the ball valve handle is under the RBVS plunger, a spring-loaded
actuator will contact the valve handle. When the handle is moved from
the position, this actuator extends to the tripped position, and the RBVS
contacts change state, thereby opening or closing a circuit.
The unit also includes a small "L" bracket and "V" clamp to allow the
RBVS to mount directly to the nipple on the coil of a solenoid valve.
The plunger of the RBVS is actuated by the stud protruding through the
center of the coil, see Fig. 6. If a technician removes the coil from the
solenoid for testing, the RBVS will activate.
a cover tamper switch is available and is activated by the removal of the
RBVS housing cover. If an attempt is made to remove the RBVS by the
removal of the mounting brackets, the unit will be set into the tripped
mode by this action.
The RBVS can be mounted to the hex portion of the ball valve or back-
flow-preventer or to the adjoining pipe via two clamps. The RBVS is
shipped with three sets of mounting kits to accommodate various pipe
and valve sizes, refer to Table 1. an "L" shaped and offset bracket for
mounting the switch enclosure and an extension bracket add to the
mounting flexibility of the RBVS. See "Typical Mounting Diagrams"
and "Installations and Operation" on following pages.
Potter Electric Signal Company, LLC
Technical Specifications
Dimensions
Shipping
Weight
enclosure
Temperature
Range
Optional
Housing Cover
Tamper
Contact
Ratings
environmental
Limitations
Conduit
entrance
*Specifications subject to change without notice.
St. Louis, MO
5401591 - REV A
1/20
firealarmresources.com
Universal Ball Valve/Solenoid
Coil Supervisory Switch
With Large Clamps: 6" L x 5" W x 5.3" H (15,2 cm L
x 12,7 cm W x 13,2 cm H)
With Small Clamps: 6" L x 4" W x 5.3" H (15,2 cm L
x 10,2 cm W x 13,2 cm H)
With Solenoid Clamp assembly: 5.1" L x 3.3" W x 6"
H ( 13 cm L x 8,38 cm W x 15,24 cm H)
1.65 lbs.
Non-Corrosive Composite Material
-40°F to 150°F (-40°C to 65°C)
Cover incorporates tamper resistant fasteners
that requires a special key for removal. One key
is supplied with each device. For optional cover
tamper switch kit, order Stock No. 0090224. See
bulletin #5401598
SPDT Contact: (Form C) 10.1A at 125 VAC
2A at 30 VDC Resistive
10 mAmps minimum at 24 VDC
SPDT Cover Tamper: 5A at 125 VAC
NeMa 4 (Ip66)
Not for use in hazardous locations
Use suitably rated conduit and connections
One Knockout for 1/2" conduit connection provided
(See Notice on page 6)
Phone: 800-325-3936
RBVS
1mA at 5 VDC min
www.pottersignal.com
page 1 OF 12

Publicité

Table des Matières
loading

Sommaire des Matières pour Potter RBVS

  • Page 1 Important: This document contains important information on the installation and operation of the RBVS Universal Ball Valve/Solenoid Coil Supervisory Switches. please read all instructions carefully before beginning installation. a copy of this document is required by NFpa 72 to be maintained on site.
  • Page 2: Mounting Kits

    Conduit Red Solenoid 1, 2(x2), 10 13, 21 11(x2), 12(x2), 16, 17(x4), 18, 19, 20(x2) Valve “Nipple” Mounting Kit (Fig 6) Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com • 5401591 - REV A...
  • Page 3 BRACKET EXTENSION 4.5” permits the actuator to contact the valve handle. Cut and remove HEX BOLT (18) the plastic coating from the ball valve handle to allow the RBVS WASHER (19) SCREW-TAMPER TAMPER actuator to contact and be activated by the metal of the handle.
  • Page 4 Cut and remove 1/2"-2" BALL VALVE the plastic coating from the ball valve handle to allow the RBVS GRIPPERS (2,6) actuator to contact and be activated by the metal of the handle.
  • Page 5 Attach the (bracket-mounting solenoid) from the Red bag to the RBVS through the two smaller slots in the bracket with two tamper resistant screws. 10. Slide the bracket up against the stop on the back of the RBVS and tighten the tamper resistant screws. INSERT NUTS #10-32 INTO BOTTOM CLAMP (11) 11.
  • Page 6: Ordering Information

    Coil Supervisory Switch Tamper Switch Connections Testing The RBVS and its associated protective monitoring system should be tested in accordance with applicable NFpa codes and standards and/or the authority COVER TAMPER & RBVS CONNECTED TO THE SAME ZONE ON THE FACP having jurisdiction (manufacturer recommends quarterly or more frequently).
  • Page 7: Caractéristiques

    Important : Ce document contient des informations importantes concernant l’installation et le fonctionnement des interrupteurs de surveillance du clapet à bille universel RBVS/de la bobine de solénoïde. Veuillez lire attentivement l’intégralité des instructions avant de commencer l’installation. Le NFpa 72 exige qu'une copie de ce document soit gardée sur le site.
  • Page 8: Trousses De Montage

    1/2 po 1, 2(x2), 10 13, 21 11(x2), 12(x2), 16, 17(x4), 18, 19, 20(x2) solénoïde blanche/ de 1/2 po (Image 6) transparente/rouge Potter Electric Signal Company, LLC • St. Louis, MO • Téléphone : 800-325-3936 • www.pottersignal.com • 5401591 - REV A...
  • Page 9 Placez l'assemblage du collier de serrage en afin que l'actionneur BOULON DE ACTIONNEUR RBVS entre en contact avec la poignée de la vanne à environ 1 po de 1/4-20 PO (18) son extrémité intérieure. Voir l'Image 1. pour connaître l'emplacement...
  • Page 10 (minium) de couple. 12. enlevez le couvercle de l'enceinte de l'interrupteur RBVS. 13. Faites glisser l'enceinte RBVS dans le support de montage en « L » jusqu'à ce que le boîtier entre en contact avec la poignée de la vanne en «...
  • Page 11 Serrez le boulon hexagonal sur le support de montage en « L ». MACHINE À VIS 14. Faites glisser le RBVS sur le support de montage en « L » afin que NO. 10-32 X 1 3/4 PO (12) l'actionneur soit activé par le goujon de la bobine de solénoïde.
  • Page 12: Connexions De L'interrupteur Inviolable

    Interrupteur de surveillance des crosses Connexions de l'interrupteur inviolable Test Le RBVS et son système de surveillance de protection devraient être LA PROTECTION DU COUVERCLE testés en conformité avec les codes et normes NFpa applicables et/ ET LE RBVS SONT BRANCHÉS À LA ou par l'autorité...

Table des Matières