PS40-2 with Nylon pressure connection shown
Tamper:
Cover incorporates tamper resistant fastener that requires a special
key for removal. One key is supplied with each device. For
optional cover tamper switch kit, order Stock No. 0090200. See
bulletin #5401200 PSCTSK.
Models:
PS40-1 Canadian, PS40-1 Canadian and Brass Bushing
PS40-2 Canadian, PS40-2 Canadian and Brass Bushing
Service Use:
Automatic Sprinkler
One or two family dwelling
Residential Occupancy up to four stories
National Fire Alarm Code
Installation
The Potter PS40 Series Supervisory Pressure Actuated Switches are designed
primarily to detect an increase and/or decrease from normal system pressure
in automatic fire sprinkler systems. Typical applications are: Dry pipe
systems, pre-action air/nitrogen supervision, pressure tanks, air supplies,
and water supplies. The PS40 switch is factory set for 40 PSI (2,8 BAR)
normal system pressure. The switch marked with the word LOW is set to
operate at a pressure decrease of 10 PSI (,7 BAR) at 30 PSI (2,1 BAR). The
switch marked with the word HIGH is set to operate at a pressure increase
of 10 PSI (,7 BAR) at 50 PSI (3,5 BAR). See section heading Adjustments
and Testing if other than factory set point is required.
1. Connect the PS40 to the system side of any shutoff or check valve.
2. Apply Teflon tape to the threaded male connection on the device. (Do
not use pipe dope)
3. Device should be mounted in the upright position.(Threaded
connection down)
4. Tighten the device using a wrench on the flats on the device.
Wiring Instructions
1. Remove the tamper resistant screw with the special key provided.
2. Carefully place a screwdriver on the edge of the knockout and sharply
apply a force sufficient to dislodge the knockout plug. See Fig. 9
3. Run wires through an approved conduit connector and affix the
connector to the device. A NEMA-4 rated conduit fitting is required
for outdoor use.
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-0988/Canada 888-882-1833 • www.pottersignal.com
PRINTED IN USA
SUPERVISORY PRESSURE SWITCH
UL, cUL, and CSFM Listed, FM and LPC Approved, NYMEA
Accepted, CE Marked
Dimensions: 3.78" (9,6cm)W x 3.20" (8,1cm)D x 4.22" (10,7cm)H
Conduit Entrance:
Two knockouts provided for ½" conduit. Individual
switch compartments and ground screw suitable for
dissimilar voltages.
Enclosure:
Cover- Die-cast with textured red powdercoat finish, single
cover screw and rain lip.
Base- Die-cast
Pressure Connection:
Nylon or Brass ½" NPT male
Factory Adjustment:
PS40-1 operates on decrease at 30 PSI (2,1 BAR)
PS40-2 operates in increase at 50 PSI (3,5 BAR) and on decrease
at 30 PSI (2,1 BAR)
Pressure Range:
10-60 PSI (0,7 - 4,1 BAR)
Differential:
Typical 1 lb. at 10 PSI (,07 at ,7 BAR)
4 lbs at 60 PSI (,28 at 4,1 BAR)
Maximum System Pressure:
300 PSI (20,68 BAR)
Switch Contacts:
SPDT (Form C)
10.1 Amps at 125/250VAC, 2.0 Amps at 30VDC
One SPDT in PS40-1, Two SPDT in PS40-2
Environmental Specifications:
NFPA-13
NEMA 4/IP66 Rated Enclosure - indoor or outdoor when used
NFPA-13D
with NEMA 4 conduit fittings.
NFPA-13R
Temperature range: -40°F to 140°F (-40°C to 60°C)
NFPA-72
4. Connect the wires to the appropriate terminal connections for the
service intended. See Figures 2,4,5,6, and 8. See Fig. 7 for two switch
one conduit wiring.
Adjustment And Testing
The operation of the pressure supervisory switch should be tested upon
completion of installation and periodically thereafter in accordance with
the applicable NFPA codes and standards and/or the authority having
jurisdiction (manufacturer recommends quarterly or more frequently).
Note: Testing the PS40 may activate other system connected devices.
The use of a Potter BVL (see product bulletin 5400799 for details) is
recommended to facilitate setting and testing of the PS40 pressure switch.
When a BVL (bleeder valve) is used, the pressure to the switch can be
isolated and bled from the exhaust port on the BVL without effecting the
supervisory pressure of the entire system. See Fig. 3
The operation point of the PS40 Pressure Switch can be adjusted to any
point between 10 and 60 PSI (0,7 - 4,11 BAR) by turning the adjustment
knob(s) clockwise to raise the actuation point and counter clockwise to
lower the actuation point. In the case of the PS40-2, both switches operate
independent of each other. Each switch may be independently adjusted to
actuate at any point acrosss the switch adjustment range. Initial adjustment
can be made with a visual reference from the top of the adjustment knob
across to the printed scale on the switch bracket. Final adjustments should
be verified with a pressure gauge.
MFG. #5400931 - REV G
09/12
PS40
PAGE 1 OF 8

Publicité

loading

Sommaire des Matières pour Potter PS40

  • Page 1 The operation of the pressure supervisory switch should be tested upon and water supplies. The PS40 switch is factory set for 40 PSI (2,8 BAR) completion of installation and periodically thereafter in accordance with normal system pressure.
  • Page 2 PS10 will render the PS10 inoperative. To comply with IBC, IFC, BLEEDER VALVE ALARM TEST PRESSURE and NFPA-13, any such valve shall be electrically supervised with a CHECK VALVE SWITCH VALVE supervisory switch such as Potter Model RBVS. WATER MOTOR GONG RBVS CHECK VALVE DRY PIPE VALVE WATER BY-PASS DWG.
  • Page 3: High Pressure Switch

    PS40 SUPERVISORY PRESSURE SWITCH Fig. 5 Low Pressure Signal Connection Fig. 6 High Pressure Signal Connection TO FIRE ALARM PANEL TO FIRE ALARM PANEL EOLR EOLR Fig. 7 One Conduit Wiring Fig. 8 Switch Operation Break out thin section of divider to provide path for wires when wiring both (With normal system pressure) switches from one conduit entrance.
  • Page 4 Potter Electric Signal Company of St. Louis, MO., or equivalent The cover of the pressure switch shall be zinc die-cast with rain shall be connected in line with the PS40 to provide a means of lip and shall attach with one tamper resistant screw. The pressure testing the operation of the supervisory switch.
  • Page 5 Le commutateur PS40 est réglée en usine pour une pression normale de système de 40 NOTA : La vérification du PS40 peut activer d’autres dispositifs liés au système.
  • Page 6 Lors de l'utilisation de fils échoués, de l’ouverture et une perte de signal. capturer tous les volets dans le cadre de la plaque de serrage. Applications Courantes Pour Le Système D’extincteur Fig. 3 PS40 COMMUTATEUR DE SURVEILLANCE DE PRESSION ROBINET D’ARRÊT POUR VALVE CONDUIT D’AIR COMMUTATEUR La fermeture d’un robinet d’arrêt entre le clapet anti-retour d’alarme et le...
  • Page 7 PS40 COMMUTATEUR DE SURVEILLANCE DE PRESSION Fig. 5 Connexion Du Signal De Pression Faible Fig. 6 Connexion Du Signal Haute Pression VERS LE PANNEAU D’INCENDIE VERS LE PANNEAU D’INCENDIE RÉSISTANCE RÉSISTANCE D’EXTRÉMITÉ D’EXTRÉMITÉ DE LIGNE DE LIGNE COMM. COMM. Fig. 8 Fonctionnement Du Commutateur Fig.
  • Page 8 Un robinet de purge BVL, fourni ainsi l’utilisation de tensions différentes pour chaque commutateur. par Potter Electric Signal Company de St. Louis, MO., ou un modèle Le couvercle du commutateur de pression sera fait de zinc équivalent doit être branché...