Appendix 1: Wattmeter
3.
Access the Configuration menu by pressing
the joystick for 3 seconds. A passkey will be
requested. By default, this key is 0. Once you
have entered the key press the joystick once to
accept.
4.
Accepting this gains access to the password
configuration screen CNG PASS. It is
recommended that you do not modify the value
and move the joystick right to move to the next
screen.
5.
APPLICAT application type Screen. Select
the application type H in this screen. To do
this press the joystick once. At the bottom of
the display PRG appears, indicating that it is
possible to modify the value. Move the joystick
in any of the 4 directions until TYP.H appears.
Press the joystick once to accept.
6.
Move to the SYS system type selection
screen using the joystick. Press the joystick
once (the PRG indication will appear on the
bottom of the display). Move the joystick in
any of the 4 directions until 1P (in single-
phase installations) or 3P.N (in three-phase
installations) is reached. Press the joystick
once to accept.
7.
In the case of the A65+ wattmeter, move to
the transformation ratio selection screen CT
RATIO (from 1.0 to 60.00 k). For example,
if the primary current of the transformer is
3000 A and the secondary current is 5 A, the
transformation ratio is 600
8.
Move to the ADDRESS node number screen
using the joystick. Press the joystick once (the
PRG indication will appear on the bottom of
the display). Move the joystick in any of the
4 directions to indicate the wattmeter´s node
number. Press the joystick once to accept.
AAX2022IQM01_ - Installation and Operation Manual
PASS?
0
PRG
CnG PASS
0
Applicat
typ.H
PRG
SYS
1p
PRG
SYS
3p.n
PRG
CT RATIO
600
PRG
ADDRESS
1
PRG