Rail size 2 (12 mm x 4 mm/0.47 inch x 0.16 inch) max. 110 A
Connection
Solid
cross-section
Stranded
When connecting two conductors to the same terminal, the two conductors must be identical.
They must both be solid or stranded, and must be the same size and type. It is important to
tighten all terminal screws, including unused screws, to the below specified tightening torque.
Modification of PE10 earthing rail for installation of 6 to 1/0 AWG conductors.
1
Rail size 3 (18 mm x 6 mm/0.71 inch x 0.24 inch) max. 320 A
Connection
Solid and stranded
cross-section
It is important to tighten all terminal screws, including unused screws, to a torque of 53 lbf-in.
212727 / 815060300170
2021-02-25·IO00·III·en·02
1 x 12 to 10 AWG
2 x 12 to 10 AWG
1 x 12 to 6 AWG
2 x 12 to 6 AWG
1
2
1 x 2 to 2/0 AWG
2
Mounting and Installation
Terminal boxes
Series 8150/1, Series 8150/2
US
US
US
US
US
US
US
US
US
US
US
US
US
US
14270E00
US
US
US
US
US
US
US
US
14272E00
US
US
US
14271E00
29