Possible cause:
1. Incorrect placement
2. Dirty or defective
Proposed solution:
1. Position the detector as shown in Fig. 9.
2. Clean the detector as prescribed. If the lens is
defective, the detector must be replaced.
Operation & maintenance
Contact a qualified electrician in case of a fault or breakdown.
Technical data
Input:
Supply voltage ............................................. 230 V ± 10%, 50Hz
Load ............................................................ max. 40 mA
Power consumption .................................... approx. 2 W
Signal from light sensor ............................... 0-10 V
Output:
Relay ............................................................... µ 10 A,
Max. compensation capacity ......................... 140 µF
Max. stating current ........................................ 165 A/20 m sec.
Incandescent and halogen lamps .................. 2300 W cos ϕϕ = 1
Fluorescent tubes ........................................... 1200 VA cos ϕ ≥ 0.5
Fluorescent tubes HF-ballast ......................... 1200 VA cos ϕ ≥ 0.9
Halogen electronic transformer ...................... 500 VA
LED elektronic driver ....................................... 500 VA
LED lamps 230 V AC ...................................... 350 W
Energy-saving lamps, CLFi ............................. 58 pcs. (18 W)
Secondary voltage .......................................... 24 V DC ±10%
Ripple .............................................................. max. 0,5 Vpp
Performance:
Motion detector 41-262 .............................. max. 8 pcs.
Lux range ..................................................... 3-300lx or
Setting range ............................................... 3-270lx or
Tolerance of lux range ................................. ±10 %
Off delay ...................................................... 0 - 60 min.
Positive hysteresis ....................................... 10 %
Protection class ........................................... IP 20
Insulation class ............................................ Class II product
Ambient temperature ................................... +5°C ... +50°C
Approvals:
CE according to ........................................... EN 60669-2-1
Accessories
Indoor:
Motion detector ........................................... 41-262
Light sensor ................................................. 43-197
Outdoor:
Motion detector ........................................... 41-262
Light sensor ................................................. 43-198
Servodan A/S | Tel +45 7442 4726 | Fax + 45 7442 4035 | info@servodan.dk | www.servodan.com
(no short circuit
protection)
250/400 V AC, NO
800 A/200 µ sec.
30-3000lx or
300-30000lx
30-2700lx or
300-27000lx
GB
9(23)