iTEMP TMT71, TMT72
Hazardous area
Zone 0, 1, 2
EPL Ga, Gb, Gc
Safety
instructions:
Installation
Endress+Hauser
Area
Zone 1, 2
EPL Gb, Gc
+
-
5
6
3
4
• Pay attention to the installation and safety instructions in the
Operating Instructions.
• Install the device according to the manufacturer' s specifications and
the applicable standards and guidelines (e.g. EN/IEC 60079-14).
• When installing the device, the IP20 protection rating of the housing
must be maintained in accordance with EN/IEC 60529.
• If the measuring device is interconnected with certified, intrinsically
safe circuits of category "ib" with explosion protection group IIC or IIB,
the type of protection changes: Ex ib IIC or Ex ib IIB.
• The use of the CDI interface for configuration in hazardous areas is
not permitted.
Non-hazardous area
Certified associated
intrinsically safe device,
e.g RN221N
Associated intrinsically
safe devices with max.
connection values from
-
the following table
(DIN rail transmitter)
XA01736T
A0041405-EN