E C D - 0 0 2 d i s p l a y / k e y p a d u n i t : ( L E D s a n d b u t t o n f u n c t i o n s )
Blinking: valve is opening
ON: valve is fully open
Blinking: valve is closing
ON: valve is fully close
ON: demand
OFF: no demand
ON: alarm
Prg&Sel (5 sec)
OFF: no alarm
Manual reset for
blinking alarm codes
S e t u p o f ma i n p a r a me t e r s u s i n g E C D - 0 0 2 :
(need to be checked/modified before start-up)
• Make sure that digital input is 0V (open). Turn the power supply ON.
• Important: Three main parameters i.e. refrigerant type (u0), pressure sensor type
(uP) and valve type (ut) can be set only when digital input is open (0V) while the
power supply is ON (24 V). This feature is for added safety to prevent accidental
damage of compressors and other system components.
• For easy setting of main parameters, follow the pictorial procedure of "Quick
start-up" on the attached individual paper.
• Once the main parameters have been selected/saved the EC3 is ready for
startup. All other parameters can be modified at any time during operation
or standby if it is necessary.
P r o c e d u r e f o r p a r a me t e r s m o d i f i c a t i o n u s i n g E C D - 0 0 2 :
• The parameters can be accessed via the 4-button keypad. The configuration
parameters are protected by a numerical password. The default password is "12".
To select the parameter configuration:
• Press the PRG button for more than 5 seconds. A flashing "0" is displayed
• Press
or
until "12" is displayed; (password)
• Press SEL to confirm password
• Press
or
to show the code of the parameter that has to be changed;
• Press SEL to display the selected parameter value;
• Press
or
to increase or decrease the value;
• Press SEL to temporarily confirm the new value and display its code;
• Repeat the procedure from the beginning "press
• To exit and save the new settings: Press PRG to confirm the new values and
exit the parameters modification procedure.
• To exit without modifying any parameters: Do not press any button for at least
60 seconds (TIME OUT).
R e s e t a l l p a r a me t e r s t o f a c t o r y s e t t i n g :
• Make sure that digital input is 0V (open).
• Press
and
together for more than 5 seconds. A flashing "0" is displayed.
• Press
or
until the password is displayed (Factory setting = 12).
If password was changed, select the new password.
• Press SEL to confirm password
"0" is displayed.
• Press SEL to reset all parameters to factory setting
• Press PRG to activate the function and leave the special function mode.
C o n t r o l ( v a l v e ) s t a r t - u p b e h a v i o r : ( P a r a me t e r u u a n d u 9 )
EX4/5/6 ≤ 1.5 seconds
EX7 ≤ 3.2 seconds
uu
EX8 ≤ 7.2 seconds
≤ 7.3 seconds
FX5-8
FX9 ≤ 9.7 seconds
Emerson Climate Technologies GmbH
Am Borsigturm 31 I 13507 Berlin I Germany
EC3-X33 Superheat Controller and ECD-002
Keypad / Display Unit
Parameters setting/saving
Next parameter/
value (higher)
Selecting/confirming
or
to show..."
%
Sec.
u9
www.emersonclimate.eu
Operating instruction
M a i n p a r a me t e r s :
(must be checked and modified if necessary)
Code
Parameter description and choices
H5 Password
u0 System refrigerant
0 = R22 1 = R134a
5 = R410A
8 = R407A
12 = R449A
uP Installed pressure sensor type
0 = PT5-07x (for R22 / R134a / R507 / R404A / R407A / R407C /
1 = PT5-18x (for R410A/ R32)
2 = PT5-30x (for R410A / R744 / R32)
Next parameter/
3 = PT5-50x (for R744)
value (lower)
ut
Installed valve type
1 = EX4
5 = EX8
9 = FX7
O p t i o n a l p a r a me t e r s :
(recommended factory setting for majority of applications)
Code
Parameter description and choices
uu Start valve opening (%)
u9 Start opening duration (second)
uL Low superheat alarm function
0 = disable (for flooded evaporator)
1 = enable auto reset
Cut-out at 0.5K (if it maintains 1 min.); Cut-in immediately at 3K
u5 Superheat set-point (K)
If uL enabled (auto or manual)
If uL disabled
u2 MOP function
0 = disable 1 = enable
u3 MOP set-point (°C) saturation temperature
**) Factory setting is according to selected refrigerant (u0):
+13°C - R22
+7°C - R404A
+50°C - R124
+10°C - R407F
+12°C - R449A
+24°C - R1234ze
*) Min. and Max. setting values are dependant to selected type of
refrigerant
┌┘
5 Units conversion (only for u3, u5,
0 = °C, K, bar 1 = °F, R, psig
(Psig values are divided by 10. Example: Display 12.5 is 125 psig)
┌┘
1 Value to show
0 = Measured superheat (K) 1 = Measured evaporating pressure, (bar);
2 = Valve opening (%)
4 = Calculated evaporating temperature (°C) from the pressure
u4 Superheat control mode
0 = Standard,
2 = intermediate control
b1 Battery error management, when battery is
defective, see below
value
0
1
2
3
When setting b1 to option 0 or 1, the user must ensure appropriate
!
safety precautions are in place to protect the system against damage
caused by a power failure.
uF Control range valve %
*) Notes for R32: R32 is classified as low flammable refrigerant in Europe. EC3-
X33 is designed under consideration of European safety standards and directives
for none flammable refrigerants. The use of EC3-X33 with R32 is for
systems/regions which it does not require consideration of additional safety
standards as for flammable refrigerant.
After selecting the parameters the EC3-X33 is fully functional without
keypad/display unit. ECD-002 may be removed or connected at any time.
Date: 03.04.2017
2 = R507 3 = R404A
6 = R124 7 = R744 (subcritical application)
9 = R407F
10 = R32*
13 = R450A
14 = R513A
R407F / R124 / R448A /R449A / R450A / R513A /
R1234ze)
2 = EX5
3 = EX6
6 = FX5
7 = FX6
10 = FX7.5
11 = FX8
2 = enable manual reset
+15°C - R134a
+15°C - R407C
-5°C - R744
+10°C - R32
+19°C - R450A
┌┘
1)
3 = Measured coil-out temperature (°C)
1 = Slow
Alarm
display
Alarm relay
Valve
-
-
Regulating
Ab
-
Regulating
Ab
Signalling
Fully close
Ab
Signalling
Fully close
(blinking)
EC3-X33_OI_ML_R12_865009.docx
Factory
Field
Min Max
setting
setting
1
199
12
0
16
1
4 = R407C
11 = R448A
15 = R1234ze
0
3
0
1
12
5
4 = EX7
8 = FX6.5
12=FX9
Factory
Field
Min Max
setting
setting
0
100
50
0
120
5
0
2
1
3
30
6
0.5
30
6
0
1
1
*
*
**
+7°C - R507
+15°C - R410A
+10°C - R407A
+12°C - R448A
+13°C - R513A
0
1
0
0
4
0
0
2
0
0
3
2
Reset possibility after
recovery/replacement
-
-
Auto
Manual
5
100
100