Residual Hazards - Lenze EZN30110H030 Serie Instructions De Montage

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

2.2

Residual hazards

{
Danger!
Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains
disconnection.
Possible consequences:
ƒ
Protective measures:
ƒ
ƒ
{
Danger!
Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ
Protective measures:
ƒ
(
Stop!
No device protection if the mains voltage is too high
The mains input is not internally fused.
Possible consequences:
ƒ
Protective measures:
ƒ
ƒ
EDKZNXXXX−002 DE/EN/FR 3.0
All manuals and user guides at all-guides.com
Death or severe injuries when touching the power terminals.
Switch off the power supply and wait for at least three minutes before
working on the power terminals.
Make sure that all power terminals are deenergised.
Death or severe injuries when the device is touched in the event of a fault.
Implement the actions required in the EN 61800−5−1. Especially:
– Fixed installation
– PE connection must conform to standards (PE conductor diameter
³ 10 mm
2
or PE conductor must be connected twice)
Destruction of the device if the mains voltage is too high.
Observe the maximally permissible mains voltage.
Fuse the device correctly on the supply side against mains fluctuations and
voltage peaks.
l
Safety instructions
Residual hazards
2
29

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ezn30080h042 serieEzn30055h060 serieEzn30037h090 serieEzn30030h110 serieGlobal drive ezn30110h030 serieGlobal drive ezn30080h042 serie ... Afficher tout

Table des Matières