N2PS PUSHBUTTON – MOMENTARY CONTACT
Color of
Contact
operator
symbol
Natural
Red
Green
N2PL(U) PILOT LIGHT INSTALLATION
Jewel assembly
1/4" maximum
panel thickness
Locking nut
Body
Figure 4 – N2PL(U) pilot light – detail view
1.
If pilot light is completely assembled, remove transformer (when used) or transformer/
terminal block assembly by removing #4-40 screw assembly and then locking nut.
For N2PLU series, disconnect wires from terminal block and remove #4-40 screw to
remove terminal/mounting block sub-assembly.
2.
Insert body through enclosure cover from the front side, positioning marking plate and
gasket in proper location above the jewel assembly.
3.
Install and tighten locking nut to 10-15 in.-lb. torque to secure body to enclosure cover.
4.
Install transformer (when used) or transformer/terminal block assembly to body using
#4-40 screw assembly. Connect white (or yellow) transformer leads to lamp socket
leads using wire nuts provided. The N2SU series must use butt splice connectors to
connect the secondary wires on the transformer to the pilot light.
5.
Connect power source wires to proper conductors of pilot light assembly. Use the
black wires of transformer (when used) or black and white wires of lamp socket. The
N2PLU series must use the terminal block and mounting hardware provided.
Black
Power
source
Black
Figure 5 – wiring diagram
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Eaton's
Crouse-Hinds Division's "Terms and Conditions of Sale," and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever
in connection therewith.
1 circuit
2 circuit
Catalog
Contact
Catalog
number
symbol
number
Table 2
Marking plate
Gasket
#4-40 screw assembly
(when used)
Transformer
(when used)
Black
White (or
yellow)
White (or
White
yellow)
Transformer
(where used)
Eaton's Crouse-Hinds Division
1201 Wolf Street Syracuse, NY 13208 • U.S.A.
Copyright© 2018
Pilot light lamp only
Sylvania 120 MB, 3 watt (or factory sealed 120V LED lamps)
Pilot light device with jewel
Pilot light
N2PL(U)10†
N2PL(U)20†
N2PL40†
N2PL50†
†Specify jewel color for each pilot light:
Color
Symbol
Red
J1
Green
J3
Amber
J6
To avoid the risk of water ingress, make sure that the cover gasket and body
flanges are free of any foreign substance before mating.
1.
Place cover on body and securely tighten the captive cover screws. DO NOT exceed
35 in.-lbs. of torque on enclosure cover screws.
2.
The installation is complete and electrical power source may be turned ON.
FIELD REPLACEMENT
To avoid the risk of electrical shock, electrical power must be OFF before and
during installation and maintenance.
To avoid the risk of explosion, do not substitute components, as this may impair
suitability for Class I, Division 2.
1.
Remove cover from enclosure.
2.
Disconnect wiring to device to be replaced. Identify each wire for proper reassembly
to replacement device.
3.
N2SW and NSW-M6 selector switch:
a.
N2SW and NSW-M6: remove cap screw and knob, then locking nut and locking
plate.
b.
NSW and NSW-M2: remove threaded guard and locking plate.
c.
Remove assembly from back side of enclosure cover or panel.
d.
Install N2SW selector switch following New Installation information section of
these instructions.
4.
N2PS and NPB pushbutton assembly:
a.
Remove guard, marking plate and pushbutton locking plate (suffix S708 only).
b.
Remove assembly from back side of enclosure cover or panel.
c.
Install N2PS pushbutton assembly following New Installation information sec-
tion of these instructions.
5.
N2PL(U) pilot lights:
a.
Remove transformer or transformer/terminal block assembly (when used) and
locking nut. Remove body and nameplate from front side of enclosure cover or
panel.
b.
Install N2PL pilot light assembly following New Installation information section
of these instructions.
6.
Place cover on body and securely tighten the captive cover screws. DO NOT exceed
35 in.-lbs. of torque on enclosure cover screws.
7 .
The installation is complete and electrical power source may be turned ON.
PERIODIC MAINTENANCE
Perform visual, electrical, and mechanical checks of all components on a regular
schedule. This should be determined by the environment and frequency of use, but it is
recommended that checks be made at least once a year.
Lamp
PILOT LIGHT LAMP REPLACEMENT
To avoid the risk of electrical shock, be sure electrical power is OFF before
replacing the lamp.
Replacement of the pilot light lamp is easily made by unscrewing the jewel assembly. It is
not necessary to remove the cover.
Pilot light lamp only:
Sylvania 120 MB, 3 watt
For lamp replacement of the N2PLU, the complete pilot light assembly must be replaced.
ELECTRICAL RATINGS
Pilot lights:
Selector switches and pushbutton stations:
Primary power source
voltage range
Transformer
120V, 50-60 Hz
–
220-240V, 50-60 Hz
220/110
440-480V, 50-60 Hz
440/110
550-600V, 50-60 Hz
550/110