N2PS pushbutton assembly, N2SW selector switch &
N2PL pilot lights
Installation & maintenance information
N2PS pushbuttons, N2SW selector switches and N2PL pilot lights are designed for field
installation as additional or replacement control devices mounted in Eaton's Crouse-Hinds
series NCS/N2S enclosures made of Krydon
This equipment is suitable for use in Class I, Division 2, Groups B, C, D or non-hazardous
locations only.
INSTALLATION
To avoid the risk of explosion, do not disconnect equipment unless power has
been switched off or the area is known to be non-hazardous and free of ignitable
concentrations.
To avoid the risk of electrical shock, electrical power must be OFF before and
during installation and maintenance.
1.
Remove front cover from enclosure. For field addition, prepare cover hole in enclosure
following hole pattern diagram in Figure 1.
Minimum cover thickness: 1/16"
Maximum cover thickness: 1/4"
Figure 1 – hole pattern
N2SW SELECTOR SWITCH INSTALLATION
Locking nut
Locking plate
1/4" maximum
panel
thickness
Gasket(s)
Cam module
Switch assembly
Figure 2 – N2SW selector switch – detail view
1.
If selector switch is assembled, remove cap screw, knob, locking nut and locking plate.
2.
Select one (1) gasket when mounting switch to Krydon enclosure, or use up to three
(3) gaskets when mounting switch on panel thickness less than 1/4" .
3.
Place gasket(s) in position and then insert switch assembly through cover hole from
back side of enclosure cover or panel.
4.
Install locking plate and secure with locking nut. Tighten locking nut to 10-15 in.-lb.
torque to secure switch assembly to enclosure cover.
5.
Install knob and secure to switch assembly with cap screw.
6.
Connect wiring to switch terminals following your system wiring pattern. See Table 1
for contact arrangements.
IF 1084 • 08/18
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
®
material, other enclosures or on panels.
! WARNING
! WARNING
Cap screw
Knob
Copyright © 2018, Eaton's Crouse-Hinds Division
N2SW TYPE SELECTOR SWITCHES
Cat. No.
Unit
Two-position
Two circuit
Two-position
Four circuit
Three-position
Two circuit
Radius
Three-position
Four circuit
Three-position
Four circuit
NOTE: For three-position selector switches with suffix S634, Position 3 is momentary
contact with spring return to Position 2. For three-position selector switches with suffix
S635, Position 1 is momentary contact with spring return to Position 2.
N2PS PUSHBUTTON ASSEMBLY INSTALLATION
1/4" maximum
panel thickness
Gasket(s)
Switch assembly
1.
If pushbutton is completely assembled, unthread and remove guard, marking plate
and pushbutton locking plate (suffix S708 only).
2.
Select one (1) gasket when mounting switch to Krydon enclosure, or use up to three
(3) gaskets when mounting switch on panel thicknesses less than 1/4''.
3.
Place gasket(s) in position and then insert switch assembly through cover hole from
back side of enclosure cover or panel.
4.
Install non-metallic plate (suffix S708 only) and marking plate, then secure with
threaded guard. Tighten guard to 65-70 in.-lb. torque. (Remove 1/4 turn spacer if
required to align lockout bar, S708 only).
5.
Connect wiring to switch terminals following your system wiring pattern. See Table
2.
Panel position
Contact arrangement
(front)
Position
Table 1
Pushbutton
Figure 3 – N2PS pushbutton assembly – detail view
IF 1084
Position
Position
Guard
1/4 turn spacer
(suffix S708 only)
Marking plate
Non-metallic plate with
bead chain and bar
(suffix S708 only)
Page 1

Publicité

loading

Sommaire des Matières pour Eaton Crouse-Hinds N2PS

  • Page 1 SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE N2SW TYPE SELECTOR SWITCHES N2PS pushbuttons, N2SW selector switches and N2PL pilot lights are designed for field installation as additional or replacement control devices mounted in Eaton’s Crouse-Hinds Cat. No. Panel position Contact arrangement series NCS/N2S enclosures made of Krydon ®...
  • Page 2 Heavy duty, 600 VAC maximum, A600 All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Eaton’s Crouse-Hinds Division’s “Terms and Conditions of Sale,” and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.
  • Page 3 ; S708 uniquement.) Raccorder les fils aux bornes du sélecteur en se référant au schéma de câblage du circuit. Voir Tableau 2. IF 1084 • 08/18 Copyright © 2018, Eaton’s Crouse-Hinds Division Page 1...
  • Page 4 Conformément aux Modalités de vente de Crouse-Hinds, et du fait que les conditions d’utilisation sont en dehors de notre contrôle, l’acheteur doit déterminer la pertinence du produit en regard de l’utilisation prévue et il assume tous les risques et responsabilités, de quelque nature que ce soit, qui s’y rapportent. Eaton’s Crouse-Hinds Division IF 1084 1201 Wolf Street Syracuse, NY 13208 •...